For full functionality of this site it is necessary to enable JavaScript.
EMIN.VN
0

How does the Kyoritsu 4105A measure earth resistance? Quick review and usage instructions.

2026年03月06日 10時57分24秒

When inspecting the grounding system in electrical cabinets, buildings, or factories, measuring the ground resistance is almost mandatory. If the ground resistance value is not met, the lightning protection and electrical protection system will not function as designed.

Among the popular earth resistance meters currently available, the Kyoritsu 4105A is a popular choice due to its simple operation, portability, and a measurement range suitable for most subsequent testing needs. This article will help you understand how this model is used in various situations and how to perform practical measurements.

What applications are Kyoritsu 4105A used for?

In practice, earth resistance meters are commonly used when testing grounding systems in:

- Electrical cabinets in factories

- Building lightning protection systems

- Small substations or residential electrical systems

- Grounding systems for machinery

During the measurement, we check the resistance value between the grounding system and the ground. If the resistance is too high, leakage current or lightning current will have difficulty dissipating into the ground, reducing the effectiveness of the system's protection.

For such routine inspections, the Kyoritsu 4105A is often carried by many technical teams due to its compact size and familiar measurement method.

Key points to note when using Kyoritsu 4105A

Upon holding the device, the most noticeable features are its compact size and clearly arranged control buttons. The device uses a rotary knob to select the measurement range, an LCD screen to display results, and a "PRESS TO TEST" button to begin measurements.

Key features include:

- Display screen showing measured values

- Rotary knob for selecting the measurement range

- Indicator light during measurement

- Test lead connector

- Included grounding rods

The device also has a sturdy protective casing, making it suitable for outdoor use without significant risk of minor impacts during operation.

Measurement range of Kyoritsu 4105A

The Kyoritsu 4105A is designed for common grounding measurements in electrical systems.

Key specifications include:

- Ground resistance measurement range: 0 - 2000 Ω

- Accuracy: approximately ±2%

- Ground voltage measurement range: 0 - 200 V AC

- Current measurement range: approximately 2 mA

This range is sufficient for testing many grounding systems in factories, buildings, or construction sites.

How to measure earth resistance using Kyoritsu 4105A

Measuring grounding with this device isn't too complicated if you're familiar with the 3-stake measurement method.

Step 1: Check the battery before measuring

Turn on the device and observe the battery icon on the screen. If the battery is low, replace it before measuring to avoid errors.

Step 2: Connect the test leads and ground stakes

The device's accessories include:

- Test leads

- Auxiliary stakes driven into the ground

- Alligator clips

The auxiliary stakes need to be driven into the ground at appropriate distances from the main ground stake.

Step 3: Check Earth Voltage

Before measuring resistance, switch the device to the Earth Voltage range to check the earth voltage. If the value is lower than approximately 10V, you can proceed with measuring resistance.

Step 4: Proceed with measuring earth resistance

Turn the rotary knob to the resistance measurement range, then press PRESS TO TEST to begin the measurement. The resistance value will be displayed directly on the screen.

If the needle or screen fluctuates abnormally, check the test leads or the location of the grounding rod.

What is the acceptable earth resistance value?

The required grounding resistance varies depending on the electrical system. Some common values ​​include:

- Building lightning protection systems: approximately ≤ 10 Ω

- Industrial electrical cabinet grounding: approximately ≤ 4 Ω

Some substations or special systems may require lower values.

Regular measurements help detect poor grounding early, especially after prolonged use or after electrical system changes.

Besides Kyoritsu, what other reputable brands are there?

In the field of electrical measurement, many technicians are familiar with using long-established brands such as:

 - Hioki

- Chauvin Arnoux

- Fluke

These brands all offer a wide range of earth resistance meters for testing both residential and industrial electrical systems, and are all officially distributed in Vietnam by EMIN.

Who is suitable for Kyoritsu 4105A?

If your work frequently requires checking grounding at construction sites or factories, the Kyoritsu 4105A is a fairly easy-to-use model. It doesn't have too many complex functions, but its measuring range is sufficient for common grounding inspection tasks.

For many electrical maintenance teams, this is still the model they carry when they need to quickly check grounding systems on-site.

相关新闻

What Is Resonant Frequency? Why Can a Single Frequency Range Damage the Entire Product?
2026年07月10日 15時10分46秒

A device may operate stably for months, yet suffer cracks, broken solder joints, or snapped component leads after being transported. What surprises many engineers is that the vibration amplitude during transport is no greater than usual. The root cause lies in a specific frequency range where the product's structure absorbs energy most intensely, triggering resonance and causing continuous stress concentration at a single point.

Should Carton Packaging Undergo Vibration Testing or Drop Testing First?
2026年07月10日 10時38分40秒

Một kiện hàng gần như không bao giờ bị rơi ngay khi vừa rời khỏi nhà máy. Quãng đường hàng trăm kilomet trên xe tải, container hay băng chuyền mới là giai đoạn diễn ra đầu tiên, nơi bao bì liên tục chịu rung lắc trong nhiều giờ. Chỉ sau đó mới đến những cú va chạm khi bốc xếp, giao nhận hoặc rơi ngoài ý muốn.

Distinguishing Between DFT and WFT in Coating Thickness Measurement
2026年07月09日 14時40分30秒

Many projects encounter a situation where a freshly applied coating looks perfectly uniform and paint consumption matches the estimate, yet additional coating is required during inspection because the thickness is insufficient. This leads many to suspect measurement errors or equipment inaccuracy, whereas the actual cause is a confusion between WFT (Wet Film Thickness) and DFT (Dry Film Thickness)

Can a car paint thickness gauge detect if a vehicle has been in a collision?
2026年07月08日 16時56分01秒

Many used car buyers often spend a considerable amount of time examining the paintwork, the gaps between body panels, or the overall condition of the exterior. However, these signs can be skillfully masked following repairs; precise color matching and careful polishing can make the vehicle appear almost factory-original.

获取优惠更新

获取专属批量折扣、批发价格更新和新产品通知,直接发送到您的邮箱。

订阅即表示您同意我们的服务条款隐私政策

快速支持

直接联系认证专家