1. 3-phase constant current source charging, charging current: 3A/1A step, 0.6A/0.2A step

2. Max. Terminal voltage: 24V

3. Max. Range of transient resistance: 100Ω

4. Measuring range of transient resistance: 1A step: 0.4Ω-20Ω; 0.2A step: 10Ω-100Ω

5. Time length of waveform recording: 300ms

6. Sampling rate: 30k

7. Time resolution: 0.1ms

8. Resistance resolution: 0.1Ω

9. Accuracy: 

Transient resistance: ±5% of the reading±0.1Ω

Transient time: ±0.5% of the reading±0.2ms

10. Working condition: Temperature -10~40℃, Humidity<85% RH