HV HIPOT GDYB-S3 Three-phase Energy Meter Test System (40~480V)

ModelGDYB-S3
原产地China
保修1 年
联系我们
安全结算
品质保证
轻松更换与退货
支持配送

Accuracy level: 0.1%

Communication port: RS232

Output voltage: 

- 3*100V/57.7V Y   3*100V  triangle                             

- 3*380V/220V Y    3*380V  triangle

- Regulating range: 0-120% consecutively adjustable

- Regulating accuracy: better than 0.01%

- Special voltage range can be setup according to actual order.

Current range: 

- 25mA, 0.1A, 1A, 5A, 25A, 100A

- Regulating range: 0-120% consecutively adjustable

- Regulating accuracy: better than 0.01%

- Minimum output current: 1mA , accuracy : <5%

Output power: (voltage loop) 3*50VA; (current loop)  3* 150VA

Stability of output voltage, current and power: ≤0.05%

Wave distortion of output voltage and current: ≤0.5%

Symmetry of three phase: better than 120°+0.3°

Frequency range: 45Hz-65Hz; Regulating accuracy: 0.01 Hz

Phase shifting range: -180.0°-180.0°; Regulating accuracy: 0.01°

 Indicating instruments class: 

- Voltmeter and ammeter accuracy: level ±0.1%

- Phase meter accuracy: ±0.01°

- Frequency meter accuracy: ±0.01Hz

Voltage input: 

- Voltage input range: 40~480V

- Input: 60, 120, 240, 480V

- Input load: ≤0.5mA, (480V)