Performance Data Temperature
Temperature range [°C]: -40…180
Temperature variation depending on setpoint [± K]: 0.5…1.5
Temperature fluctuation depending on setpoint [± K]: 0.1…0.5
Average heating-up rate according to IEC 60068-3-5 [K/min]: 5
Heating up time from -40 °C to 180 °C [min]: 75
Cooling down time from 180 °C to -40 °C [min]: 90
Average cooling down time according to IEC 60068-3-5 [K/min]: 5
Max. heat compensation at 25 °C [W]: 800
Electrical data
Rated Voltage [V]:p 230
Power frequency [Hz]: 50
Nominal power [kW]: 2.8
Unit fuse [A]: 16
Phase (Nominal voltage) [ph]: 1~
Outer dimensions
Width net [mm]: 720
Height net [mm]: 1445
Depth net [mm]: 778
Wall clearance back [mm]: 300
Wall clearance sidewise [mm]: 200
Viewing window width [mm]: 288
Viewing window height [mm]: 255
Doors
Unit doors: 1
Internal Dimensions
Width [mm]: 400
Height [mm]: 420
Depth [mm]: 350
Further Dimension
Interior volume [L]: 60
Net weight of the unit (empty) [kg]: 165
permitted load [kg]: 60
Load per rack [kg]: 15
Environment-specific data
Sound-pressure level [dB(A)]: 59
Fixtures
Number of shelves (std./max.): 1 / 4