For full functionality of this site it is necessary to enable JavaScript.
EMIN.VN
0
Product image

MADE m.PAD Phase & Feeder Identifier

Modelm.PAD
原产地France
保修1 年
联系我们
安全结算
品质保证
轻松更换与退货
支持配送

FUNCTIONS

m.PAD is a phase and feeder indicator specifying on which phase and on which feeder a customer is connected on a live low voltage network, downstream of a transformer substation. It is a robust, reliable, and user friendly system.

USE PRINCIPLE

m-PAD is composed of a transmitter and a receiver. The transmitter is connected at the transformer substation :

• On the low voltage side to the three phases and neutral.

• On each feeder with a Made-Flex current coil (around the three phases and excluding

the neutral in STAR configuration, around each phase in DELTA configuration).

The receiver can then be connected between phase and neutral (Y) or phase and phase (D) anywhere on the network to indicate the phase and feeder of the customer.

TECHNICAL CHARACTERISTICS

Tranmitter

– STAR or DELTA configuration

– 230/400 VAC (phase to phase)

– 115/230 VAC (phase to neutral)

– 50 Hz or 60 Hz

– 240 x 160 x 120 mm

– IP 54

– -15°C / + 55°C

Receiver

– 100 - 250 VAC + battery 9 V to display resuts

– 50 Hz or 60 Hz

– 195 x 100 x 60 mm

– IP 64

– -15°C / + 55°C

General

– 9,85 kg

– Cat IV voltage cords, including HPC 50 kA1,6 A/1000 V fuses

Datasheet


Manual

获取优惠更新

获取专属批量折扣、批发价格更新和新产品通知,直接发送到您的邮箱。

订阅即表示您同意我们的服务条款隐私政策

快速支持

直接联系认证专家