快速支持
直接联系认证专家
Accuracy: ± 0.5 %
Approvals: CE
Input Type: Thermocouple Type K
Input Range: -18 to 1093 °C
Cable Length: 3 m
Supply Power: 9 to 24 Vdc @ 30 mA max
Output Signal: Current
Response Time: 120 ms
Load Resistance: (Vsupply – 9V)/0.02 A
Electrical Output: 4 to 20 mA, 1 to 5 Vdc
Supply Power Type: DC
Temperature Effect: ± 0.015 mA/°C
Loop Resistance, Max: (Vs – 9V) / 0.020 A
Electrical Connection: Cable
Sensor Break Detection: Leg 1: Open = 27 mA, Leg 2: Open = 2.2 mA, Leg 3: Open = 2.2 Ma
Operating Temperature, Max: 85 °C
Operating Temperature, Min: -40 °C
Input Electrical Connection: Universal Female Thermocouple Connector