Width: 23 mm
Height: 110 mm
Length: 114 mm
Weight: 160 g
Accuracy: ± 3.5 %
Approvals: CE
Input Type: Current
Modularity: Link Concept modularity: VIBROCONTRL 1800 Series –all components -Vibration Monitor, EtherBridge, Relay Module, Input and Output Modules can be interconnected by means of DIN rail bus connectors
Capacitance: 10 nF
Input Range: 4 to 20 mA, 0 to 20 mA
Sensitivity: 10 to 500 mV/g
Sensor Type: Accelerometers CCS
Applications: Bearing Conditions, Casing Vibration, Rolling Element
Accuracy Note: Vibration Measurement:± 3.5%, Process Measurement:± 0.75%, Analogue output:± 1.5%, Speed Sensors:± 0.5%
Output Signal: Current
Test Function: Can be activated digitally or by PC. As default the alarm relays activate and DC outputs increase to the specified test level of 102 %
Approvals Note: CE, ISO 13849-1, ISO 10816-3, VDI 3832, API 670
Data Interface: USB, RS-485, Ethernet
LED Indicators: 5 light diodes indicate channel status (green, yellow, red) for each of the 4 vibration input channels, as well as for general system status
Recording Note: Up to 4 input channels can record digital raw data (time waveform) simultaneously to a PC running The recording can be done through: RS-485/LAN (buffered): Up to 10 kHz Mini USB (real-time): Up to 10 kHz Time waveform recording is user activated and contains scalar values for vibration and process input data at start of recording.
Alarm Type Note: alert_and_danger_per_each_detector_with_adjustable_alarm_limits alert_delay_time_0_100_sec danger_delay_time_0_100_sec reset_time_for_alert_and_danger_0___100_sec
Input Resistance: ≥ 450 kΩ
Electrical Output: 4-20 mA, 0-20 mA
Enclosure Ratings: IP20
Sensor Excitation: 5 mA
Frequency Response: 10 Hz – 1,000 Hz, -1 dB, 24 dB/oct. Selectable ranges e.g. 1-300/1,000 Hz, multiple filters settings 0.7-10,000 Hz Filter response: High pass and low pass filters;refer to the setup part for the specific parameters for the Cut-off freq., pass band attenuation, Stop band freq. and Stopband attenuation
Number of Channels: 4
Input Configuration: Full scale vibration measuring ranges up to 1-100 mm/s,1-300 m/s2 ,0.1-15 mm Pk Pk
Storage Temperature, Min: -40 °C
Operating Temperature, Max: 50 °C
Operating Temperature, Min: -10 °C
Input Electrical Connection: Screw Terminals