快速支持
直接联系认证专家
Power supply: 230V~ -15% +10% 50Hz
Electrical power: 1.5VA
Sensor type: SnO2 semiconductor
Gases detected: Natural gas (CH4)
Carbon monoxide (CO)
Trip threshold: 20% L.E.L. (CH4)
80 ppm (CO)
Output 1: Relay 5A@250V~ SPDT
Indications: Green LED lit: Detector ON
Yellow LED lit: Fault
Red light lit: CH4 alarm
Blue light lit: CO alarm
Red/blue alternately: CH4 + CO alarm
Buzzer: Alarm, after ~ 60 seconds
Activation time: ~ 40 seconds
Relay delay time: ~ 60 seconds
Sensor life: 5 years
Operating temp.: 0°C .. 40°C
Storage temp.: -10°C .. +50°C
Humidity limits: 20% .. 80% RH non-condensing
Protection rating: IP 42
Enclosure: Material: ABS V0, self-extinguishing
Colour: Signal white (RAL 9003)
Dimensions: 85 x 107 x 38 mm (W x H x D)
Weight: ~ 260 g