HIGH VOLTAGE PART TECHNICAL DATA:
HV DC source: 0-32 kV DC test (DC hipot); 60 mA nominal continuous current at 32 kV
Breakdown detection: 0-32 kV
Standard surge levels: 0… 8 / 0 … 16 / 0 … 32 kV; 2,432 / 2,432 / 2,432 J
Surge rate: Adjustable 3-10 sec, and single shot
Built-in prelocation: TDR,ARM ,ICE,DECAY
Sheath testing: 0-32kV
Communication ways: Wi-Fi 2.4G
Control: Auto Go APP(Android version)
Grounding detect range: ≥0.5Ω
Grounding detect set: 2~10Ω adjustable
Grounding detect accuracy: Better than 0.2Ω
Step voltage detect range: 0.5~200V(peak)
Step voltage detect set: 0.5~42V(30VAC)
Step voltage detect accuracy: Better than 0.2V
Operating temperature: -20 ~ +45℃
Storage temperature: -40 ~ +60℃
Weight: 180kg
Mains input supply: 220V AC,50/60 Hz,2kW
Dimensions (L x W x H): 900*650*703 mm
Protection class: IP43
RADAR AND CONTROL UNIT TECHNICAL DATA:
TDR setup: Physically and functionally integrated
Contorl: Wireless tablet computer and Emergency Stop Box
Display: 11.5''
Pulse generation: Bipolar
Pulse amplitude: 50v
Pulse width: 50ns ~10μs
Measuring range: 0 m-100 km, at VOP = 80 m/µs
ProRange: 0 -40dB
Resolution: 0.1m(at 172m/μs)
Accuracy: 0.001
Gain level: 6
Data rate: 200MHz
Velocity of propagation: 100-300m/μs
Multishot support: Yes, 5 HV fault traces,
Waveform storage capacity: Unlimited