直接联系认证专家

Function: ACA, leakage current, load current on-line test, suitable for electricity leakage patrol inspection of down hole and outdoor multi-conductor thick cable
Power Source: DC 3.7V chargeable lithium battery, USB charging portal, working continuously for 10h
Display Mode: Four digital LCD display, backlight function, suitable for dark place
Tested Line Diameter: Ф168mm Conductor, cable or 168mm×245mm bus bar
Measurement Range: Current: AC 10mA~9999A(50~60Hz automatically)
Resolution: 10mA
Current Accuracy
10mA~999A, ±2%±5dgt
1000A~2999A, ±3%±5dgt
3000A~9999A, ±4%±5dgt
Size of Insulation Rod: 300mm
Instrument Size: Length width thickness 310mm×270mm×52mm
Line Voltage: bare wire test 1000V below, less than 110kV with a safety insulation sheath wire. (operating with an insulation rod)
Automatic Shutdown: About 15mins after startup, the instrument will be automatically shut down to reduce battery consumption
Instrument Mass Instrument: 496g(include battery); Total mass: 2.3kg (including insulation rod and instrument box)