The transmitter panel is equipped with "power switch", "power indication", "output selection", "high, medium, low"; "output indication" and "K measurement" switching switches, and the indicator light indicates the switching position; "output-KΩ measurement" shares an output terminal, which is switched by the "output indication" and "KΩ measurement" switches; set "output 2" output terminal; square meter head indicates output and KΩ resistance. It can check the line on, off, mixed, and measure the size of the ground leakage resistance.

Output signal form: pulse period 1.34±0.15ms, width 0.2±0.1ms, intermittent period 1.8±1s

Output voltage: pulse period Upp high range greater than 1000V, medium range greater than 60V, low range greater than 30V

KΩ measurement: It can check the side line on, off, mixed and leakage group size, and determine the nature of the fault.

The “output 2” output terminal: It can output peak pulse short-circuit current 1–5A.

Output power: Pulse power greater than 2.5W (when high-end load resistance is 80kΩ).

Power supply: 8.4V.