GENY SZ-03A-K8 Three Phase Standard Meter (5V-480V, 10mA-120A)

Test voltage

- Range: 5V-480V

- Error: ±0.02%(5V-480V)

- Display range: 5.000000V-480.000V

Test current

- Range: 10mA-120A

- Error: ±0.02%(50mA-120A)  ±0.05%(10mA-50mA)

- Display range: 1.000000A-120.0000A

Power measure error

- Active power: ±0.02%(50mA-120A)

- Reactive power: ±0.05%(50mA-120A)

- Apparent power: ±0.05%(50mA-120A)

Frequency

- Range: 45Hz-65Hz

- Display range: 45.000-65.000

Phase angle

- Range: 0º – 360º

- Error: ±0.05°

- Display range: 0.000001°--359.9999°

Dimensions(WxHxD)(mm): 432x131x470

Weight(kg): 16