Temperature Range(℃ / ℉) -20 to 40 / -4 to 104
Temperature Stabilityat 15℃, (±℃ / ℉) 1 / 1.8
Cooling Capacity: at 20℃ (kw)- 1.8/ at 10℃ (kw) - 1.5/ at 0℃ (kw)- 1.15
at -10℃ (kw) - 0.85/ at -20℃ (kw) - 0.4 kw
Pump: Max. Flow Rate (L / min, gal / min) 40 lit
: Max. Pressure (bar / psi) 2.8 bar
Dimension: Overall (WxLxH, mm / inch) 515×715× 835 mm
Net Weight (kg / Ibs) 92.65 kg
Electric Requirement (230V, 60Hz) 5A/ Cat. No. AAH65131K
Electric Requirement (230V, 50Hz) 4.5A/ Cat. No. AAH65122K
Detail
Operating features
• Temperature range is from -20℃~40℃.
• Bright LED water level indicator can be easily identified.
• Low fluid level and dry-running protection when triggered shows an error symbol on the display and an
audible sound.
• If the equipment operates at 40℃ or above due to the external environment, user can simply identify the
error with a visual or an audible sound.
• Designed to simplify operation with a touch screen type display.
- Easy-to-read VFD display with interactive touch keys.
- Setting and resolution indication 0.1℃/℉.
- Quick keypad lock prevents accidental parameter changes.
- Signal indicator for operation status.
Constructional features
• The refrigerating system is designed to reduce energy consumption and to maximize in refrigerating
efficiency.
• Eco-friendly R-404A / R507 refrigerant is used to prevent environmental pollution. Double service valve is
used to prevent refrigerant leakage.
• Removable gridded vent for reducing condenser contamination and to facilitate cleanliness.
• A wide (Ø120mm / 4.72″) solution inlet is for easy and safe pouring of solution into the recirculating cooler.
• Pressure gauge comes standard for observing the pump pressure
• The refrigeration system can be observed easily to diagnostic at a glance by high / low pressure gauges.
(HL-25H, 35H, 45H, 55H models)
• Wheels allow for easy mobility.
• The beautifully designed and compact.
• Different types of pumps come standard with the recirculating cooler to provide versatility.
• Warning alarm/monitoring system.
- Over temperature.
- Lack of bath solutions.
• Variety of accessories is available to meet user’s different lab environment needs. (Refer to accessories)
|
Model |
HL
-05 |
HL
-10 |
HL
-15 |
HL
-20 |
HL
-15H |
HL
-20H |
HL
-25H |
HL
-35H |
HL
-45H2) |
HL
-55H2) |
Temperature1)
(bath fluid :
Ethtylene glycol mix
1:1 Water) |
Working Temperature
range
(℃ / ℉) |
-20 to 40 / -4 to 104
|
Temperature stability
at 15℃, (±℃ / ℉) |
1 / 1.8
|
Cooling capacity
(bath fluid : Ethtylene
glycol mix 1:1 Water) |
at 20℃ (kw) |
0.60
|
0.07
|
1.45
|
1.80
|
1.45
|
1.80
|
2.50
|
3.30
|
6.50
|
7.10
|
at 10℃ (kw) |
0.50
|
0.60
|
1.15
|
1.50
|
1.15
|
1.50
|
1.80
|
2.30
|
4.50
|
6.00
|
at 0℃ (kw) |
0.35
|
0.42
|
0.86
|
1.15
|
0.86
|
1.15
|
1.10
|
1.70
|
3.00
|
4.10
|
at -10℃ (kw) |
0.18
|
0.32
|
0.62
|
0.85
|
0.62
|
0.85
|
0.65
|
1.00
|
2.10
|
2.50
|
at -20℃ (kw) |
0.04
|
0.14
|
0.30
|
0.40
|
0.30
|
0.40
|
0.40
|
0.55
|
1.20
|
1.50
|
Pump |
Max. flow rate
(L / min, gal / min) |
50 / 13.2
|
40 / 10.57
|
70 / 18.49
|
Max. pressure
(bar / psi) |
1.0 / 14.5
|
2.8 / 40.6
|
6 / 87.0
|
Dimension |
Max,. filling capacity
(L, cu ft) |
10 / 0.35
|
15 / 0.53
|
15 / 0.53
|
25 / 0.88
|
40 /1.41
|
For tubing dia
(mm / inch) |
12.7 / 0.5
|
20 / 0.79
|
Overall
(WxLxH, mm / inch) |
405×620×710 /
15.9×24.4×28.0
|
515×715× 835 /
20.3×28.1×32.9
|
515×715× 835 /
20.3×28.1×32.9
|
550×900×1140 /
21.7×35.4×44.9
|
605×1045×1300 /
23.8×41.4×51.2
|
Net weight (kg / Ibs) |
62.85 /
138.6
|
64.85/
143.0
|
86.5 /
190.7
|
87.35 /
192.9
|
91.8 /
202.4
|
92.65 /
204.3
|
141.3 /
310.9
|
146.3 /
321.9
|
171 ±10 /
377 ±22
|
176 ±10 /
388 ±10
|
Electric requirement
(230V, 60Hz) |
5.0A
|
5.5A
|
6.5A
|
7.5A
|
6.5A
|
7.5A
|
9.5A
|
13.5A
|
|
|
Cat. No. |
AAH
65001
|
AAH
65011
|
AAH
65021
|
AAH
65031
|
AAH
65121
|
AAH
65131
|
AAH
65141
|
AAH
65151
|
-
|
| |