变压器空载和负载测试仪KVTESTER ZC-202A
制造商: KVTESTER Model: ZC-202A 来源: China - 报价要求
- 联系
Specification:
* Function : Transformer no-load current, no-load loss, short circuit voltage, short circuit (load) loss measurement.
* Working power :
Input voltage: 185Vac~250Vac
Allowable voltage : 85Vac~264Vac
Frequency : 50/60Hz
Allowable frequency: 45Hz~65Hz
Input power: 40VA
Joint: Standard AC socket 60320
*AC Voltage:
Range : 10~650V
Resolving power : 0.001V
Accuracy : 0.2%±0.001V
*AC Current :
Range : 0.5~60A
Resolving power : 0.001A
Accuracy : 0.2%±0.001A
*Frequency :
Range : 45Hz~65Hz
Resolving power : 0.001Hz
Accuracy : 0.2%±0.001Hz
*Power
Range : 0~39kW
Resolving power : 0.001kW
Accuracy : <±0.5%(CosΦ>0.1),±1.0%(0.02
*Environment condition :
Operating temperature: -10℃~+50℃
Storage temperature: -25℃~+70℃
Humidity:Relative humidity: 5%~95%,no dewing
*Physical characteristics:
Size : 360mm×220mm×150mm
Weight: ≈5kg (Excluding attachments)
Description
ZC-202A Transformer no-load & load tester can measure the transformer no-load current, no-load loss, short circuit voltage, short circuit (load) loss. Harmonic test can be carried out, analysis to the 31 harmonic. The instrument automatically switches the range, allowing the measurement of voltage, wide current range, simple wiring. Do three-phase transformer no-load, load test, the instrument can automatically determine whether the wiring is correct, and display the three-phase voltage, current vector.
Only need one tester can measure the load experiment under 1000kVA distribution transformer at full current; measuring the load test in 1/3 rated current can be completed under 3150KVA distribution transformers (in the 1/3 of the rated current under the instrument can be converted to the load loss parameters under the rated current). All test results are automatically corrected. The instrument can carry out many kinds of correction, such as waveform correction, temperature correction, non rated voltage correction, non rated current correction and so on.
Features
1. It can measure the no-load current, no-load loss, short circuit voltage and short circuit (load) loss of the transformer;
2. Harmonic test can be carried out, analysis to the 31 harmonic;
3. The instrument automatically switches the range, allowing the measurement of voltage, wide current range, simple wiring;
4. Do three-phase transformer no-load, load test, the instrument can automatically determine whether the wiring is correct, and display the three-phase voltage, current vector;
5. One can measure the load experiment under 1000KVA distribution transformer at full current; measuring the load test in 1/3 rated current can be completed under 3150KVA distribution transformers (in the 1/3 of the rated current under the instrument can be converted to the load loss parameters under the rated current);
6. All test results are automatically corrected. The instrument can carry out many kinds of correction, such as waveform correction, temperature correction, non rated voltage correction, non rated current correction and so on;
7. LCD 320 * 240 large screen, high brightness display, full menu and prompt operation English characters to realize man-machine dialogue, touch button makes the operation more convenient, wide temperature LCD with brightness adjustment, can adapt to the winter and summer season;
8. The instrument can be preset by the user 40 sets of sample parameters, and these parameters can be deleted at any time as required, and the use is very convenient;
9. Panel type thermal printer, can quickly print the results of the field test;
10. Data (test set, measurement results, test time, etc.) with the power down storage and browsing capabilities, you can store 500 sets of experimental results, and the computer can send data online;
11. Allow external voltage transformer and current transformer to expand the range measurement, can measure any parameters of the subject matter.
- 质量承诺