- Measurement Technique: Photoacoustic Infrared Spectroscopy
- Filter Capacity: Up to 5 + water
- Detection Limit: Gas dependent, but typically in the ppb region
- Repeatability: 1% of measured value
- Operating Temperature: 5 ~ 40°C (41 ~ 104°F)
- Storage Temperature: -25 ~ 55°C (-13 ~ 131°F)
- Dimensions (W x H x D): 483 mm (19") x 4U (monitor) + 4U (sampler) x 375 mm (14.8")
- Weight: 24.5 kg (53.5 lb)
Pumping System Specifications:
- Pumping Rate: 30cm3/s (flushing sampling tube) and 5 cm3/s (flushing measurement chamber)
- External Pump Performance: Distanceup to 75 m, Tube ID 3 mm, Speed 4 m/s
- Air Volume Per Sample:
Auto: Tube Length 1 m: 140 cm3/sample
Fixed Time: Chamber 2 s, Tube 3 s: 100 cm3/sample
Fixed Time: Chamber 2 s, Tube "OFF": 10 cm3/sample
- Total Internal Volume: 60cm3 (of the measurement system)
- Power Ratings: 85 VA, 100 ~ 240 VAC ± 10%, 50 ~ 60 Hz, Class 1
- Power Consumption: ≈135 VA (monitor and sampler)
- Monitor Interface: USB, Ethernet, and RS232
- Safety: EN/IEC 61010-1 3rd Edition
- Scope of Delivery: Photoacoustic gas monitor with analog/relay module, Multipoint sampler, External pump, Nylon tubing (20 m per channel), Airfilter with fittings, Remote/offline and calibration software, User manual.