Get exclusive volume discounts, bulk pricing updates, and new product alerts delivered directly to your inbox.
By subscribing, you agree to our Terms of Service and Privacy Policy.
Direct access to our certified experts
Get exclusive volume discounts, bulk pricing updates, and new product alerts delivered directly to your inbox.
By subscribing, you agree to our Terms of Service and Privacy Policy.
Direct access to our certified experts

General:
Input voltage: 100 – 260 V, 50/60 Hz
Power consumption: max. 300 VA
Reverse voltage protection: up to 13 kV
Degree of protection: IP54 (in closed state)
Data interface: USB 2.0
Dimensions (W x H x D): 438 x 456 x 220 mm
Weight (incl. HV connection cable): Approx. 22 kg
Ambient temperature (operational): -10°C to +50°C
Storage temperature: -20°C to +60°C
Safety and EMC: CE-compliant in accordance with Low Voltage Directive (2014/35/EU), EMC Directive (2014/30/EU), EN 60068-2-ff Environmental testing
User interface available in 13 languages: Czech, Chinese (CN), Chinese (TW), Dutch, English, French, German, Italian, Korean, Polish, Portuguese, Russian, Spanish
Output voltage:
Frequency range: 0.01 – 0.1 Hz
VLF truesinus®: 1 – 26 kVrms (36 kVpeak)
VLF square wave voltage: 1 – 34 kV
DC voltage: ±1 – 34 kV
Resolution: 0.1 kV
Accuracy: 1%
Load range (VLF testing): 1 nF – 8 µF
Output current:
Measurement range: 0 – 14 mA
Resolution: 1 μA
Accuracy: 1%
Max. capacitive load:
0.5 µF at 0.1 Hz, 24 kVrms / 34 kVpeak
1 µF at 0.05 Hz, 24 kVrms / 34 kVpeak
8 µF at 0.01 Hz, 18 kVrms / 25 kVpeak
Dissipation factor measurement (frida TD):
VLF truesinus®: 1 – 26 kVrms
Load range: 10 nF - 8 µF
Resolution: 1 x 10^-6
Accuracy: 1 x 10^-4
Measurement range: 1 x 10^-4 – 21,000 x 10^-3
tan δ measuring frequency: 0.1 Hz
Automatic detection and compensation of leakage currents
With VSE box (optional)
BAUR Software 4 for office PC (office installation)
Used to evaluate test and measurement logs
frida TD standard delivery
▪ frida TD VLF tester and diagnostics device, incl.
– HV connection cable, 5 m (fix mounted)
– GDR 40-136 discharge and earth rod
– Earth cable, 5 m, with earth terminal
– Jumper plug for external emergency off unit
– BAUR Software 4 for office PC (office installation)
– HV connection set
– tan delta kit
– Mains supply cord, 2.5 m
– User manual
– Additional manual for dissipation factor measurement
– Pocket guide