Get exclusive volume discounts, bulk pricing updates, and new product alerts delivered directly to your inbox.
By subscribing, you agree to our Terms of Service and Privacy Policy.
Direct access to our certified experts
Get exclusive volume discounts, bulk pricing updates, and new product alerts delivered directly to your inbox.
By subscribing, you agree to our Terms of Service and Privacy Policy.
Direct access to our certified experts

Technical data
Measuring bridge (pre-location of cable sheath faults and faults due to earth contact)
Measurement method: 4-wire measuring bridge according to Murray or Glaser
Output voltage: DC 100 V – 10 kV
Max. output current: 50 mA
Accuracy: 0.5% relating to the measurement result
Number of definable cable sections: 50
Voltage and current limitation adjustable
Step voltage method (cable sheath fault pin-pointing)
Pulsed DC voltage: 100 V – 10 kV
4 selectable pulse patterns
Max. output current: 700 mA
General
Display: LCD with background lighting, screen resolution 320 x 240 pixels, Automatic brightness setting
Reporting:
Shown on display
Automatic export via USB interface (USB 2.0)
Data export format: Text file, bilingual: English, German
Power supply:
Mains voltage AC: 100 – 240 V, 50/60 Hz
Rechargeable battery: DC 12 V, 3.4 Ah
Max. power consumption: 200 VA
Max. discharge capacitance: 25 µF
Ambient temperature (operational): -20 to +50°C
Storage temperature: -40 to +60°C
Relative humidity: Non-condensing
Weight and dimensions (W x H x D):
Shirla: Approx. 17 kg; approx. 440 x 490 x 220 mm
Transport case for accessories: Approx. 5 kg; approx. 450 x 355 x 125 mm
Degree of protection: IP54 (in closed state)
Safety and EMC: CE-compliant in accordance with Low Voltage Directive (2014/35/EU), EMC Directive (2014/30/EU), EN 60068-2-ff Environmental testing
Integrated battery
Battery type: Lead-acid battery 12 V, 3.4 Ah
Battery life: Approx. 45 min (in HV mode)
Charging time: Approx. 4 h
Cable and cable sheath testing
DC voltage: 0 – 10 kV
Output current:
10 mA @ DC 5 kV
5 mA @ DC 10 kV
Current indicator accuracy: ±10 μA
Resolution: 1 μA
Insulation resistance measurement: 0.01 MOhm to 1 GOhm
Voltage and current limitation adjustable
Standard delivery
▪ shirla sheath test and fault location device incl.
– HV connection cable, 4.5 m, fix mounted
– 4-wire bridge connection cable, 2.5 m, fix mounted
– Short-circuit cable, 1 m, 2 pcs
– G-clamps, 24 mm, 4 pcs
– Earth cable, 3 m, with earth terminal
– Transport case for accessories
– USB drive
– Carrying strap
– Mains supply cord, 2.5 m
– User manual