POWER
Output Voltage: 0 to 12 kV ac
Output Current:
Continuous @ 100 mA at 10 kV
30 minutes @ 200 mA at 10 kV
4 minutes @ 300 mA at 10 kV
Operating time period based on 50°C operating temperature.
Longer durations at high currents will be realized at lower operating temperatures.
Output Power: 3 kVA
Sinusoidal output signal internal generated independent of input supply
No loss in performance when used with portable generator.
A.C. Input:
95-264 V AC 47 to 63 Hz
16 A max at 110 V
10 A max at 220 V
TEST FREQUENCY
Range: 45 to 70 Hz independent of input signal
Resolution: 0.1 Hz
Accuracy: ± 1% of reading
TEST VOLTAGE
Range: 25 V to 12 kV
Resolution: 1 V
Accuracy: ± 1% of reading
TEST CURRENT
Range: 0 to 5.0 A
Resolution: 0.1 μA
Accuracy: ± 1% of reading, ±1 μA
CAPACITANCE
Range: 0 to 100 μF
Resolution: 0.01 pF
Accuracy: ± 0.5% of reading, ± 1 pF
INDUCTANCE
Range: 6 H to 10 MH
Resolution: 0.01 H
Accuracy: ± 0.5% of reading
WATTS
Range: 0 to 2 kW, actual
Resolution: 0.5 mW
Accuracy:
± 2% of reading at 10 kV
± 0.03% of VA, ±0.5 mW
POWERFACTOR/TAN-DELTA
Range
% PF: 0 to ± 100.00%
PF: 0 to ± 1.0000
% Tan d: 0 to ± 999.99%
Tan d: 0 to ± 9.9999
mW/Var: 0 to ± 9999.9
Resolution: 0.01% / 0.0001
Guaranteed
Accuracy
± 1% of Reading, ± 0.04%
PF/Tan d (Entire Range)
Typical Accuracy: < ± 0.005% (Entire Range)
TEMPERATURE MEASUREMENT
Range: -20°C to +50°C
Resolution: 0.1°C
Accuracy: ±4°C