Main contact inputs
• Number of contact inputs: 3 (3 x 1), 1 per phase
• Each channel detects main and pre-insertion resistor contacts.
- Closed ≤ 10 Ω,
- Resistor contacts range 10 Ω to 5 kΩ,
- Open ≥ 5 kΩ
Open circuit voltage: 20 V DC
Short circuit current 50 mA
Time measurement resolution:
• 0.025 ms for 1 s test duration (sampling rate 40 kHz)
• 0.1 ms for 2 s test duration (sampling rate 10 kHz)
• 1 ms for 20 s test duration (sampling rate 1 kHz)
• 10 ms for 200 s test duration (sampling rate100 Hz)
Time accuracy ±0,05% of the reading ± resolution
Auxiliary inputs
• Number of channels: 6, galvanically isolated
• User selectable: dry or wet
• Contact sensing (dry):
Open circuit voltage 24 V DC,
Short circuit current 5 mA
• Voltage sensing (wet):
Working voltage 300 V DC, 250 V AC
Low activation mode ± 5 V
High activation mode ±10 V
Auxiliary inputs
• Number of channels: 6, galvanically isolated
• User selectable: dry or wet
• Contact sensing (dry):
Open circuit voltage 24 V DC,
Short circuit current 5 mA
• Voltage sensing (wet):
Working voltage 300 V DC, 250 V AC
Low activation mode ± 5 V
High activation mode ±10 V
Coil resistance measurement
• 3 coils simultaneously (Open or Close)
• Measuring range / Resolution
1 Ω - 99,9 Ω / 0,1 Ω
100 Ω – 999 Ω / 1 Ω
• Typical accuracy ± (0,5 % rdg + 0,5 % FS)
Universal transducer inputs
• 3 digital travel transducer channels
Digital rotary transducers: 2500ppr
• 3 analog travel transducer channels
• Analog transducer input measurement resolution: 16 bit.
• Internal supply for linear transducer: 5 V DC
Analog inputs
• 6 channels – Coil current measurement
• 6 Voltage channels, each channel has four measurement ranges: ±1 V, ±5 V, ±60 V and ±300 V AC/DC
Static resistance measurement
• Built-in Micro Ohmmeter (200 A or 500 A)
• Current range 5 A – 200 A / 500 A
• Max. load voltage 6.2 V
• Resistance range 0.1 µΩ - 999.9 mΩ
• Resolution 0.1 µΩ
• Accuracy ± (0.1 % rdg + 0.1 % FS)
Dimensions and weight
• Dimensions (L x W x H): 505 mm x 409 mm x 257 mm (19.9 in x 16.1 in x 10.1 in)
• Weight: from 15.5 kg (34.1 lbs) up to 17 kg (37.4 lbs) depending on built-in features