Voltage generators
Output range (effective value):
6-phase AC (L–N): 6×0–120V
2-phase AC (L–L): 2×0–240V
DC (L–N): 6×0–±160V
DC (L–L): 2×0–±320V
Power:
AC (L–N): 80VA
AC (L–L): 100VA
DC (L–N): 70VA
DC (L–L): 140VA
Accuracy:
AC output: ≤0.1%
DC output: ≤0.2%
Output time: Continuous output
Resolution: 10mV
Current generators
Output range (effective value):
6-phase AC (L–N): 6×0–30A
1-phase AC (6L–L): 1×0–180A
1-phase AC (L–L): 1×0–30A
DC (L–N): 6×0–±10A
DC (3L–N): 1×0–±30A
Power:
AC (L–N): 450VA
DC (L–N): 200VA
Accuracy:
AC output: ≤0.1%
DC output: ≤0.2%
Output time:
0–10A: Continuous
10–20A: 30s
20–30A: 10s
30A: 5s
Resolution: 1mA
General
Frequency range: 0–1200Hz
Frequency resolution: 0.001Hz
Phase angle range: –360°~360°
Phase resolution: 0.1°
Time measurement range: 0.1ms–9999s
Time measurement resolution: 0.1ms
Others
PC connection: Ethernet, 10M/100M
Ground socket (earth): 4mm banana socket
Net size: 400×200×402mm
Net weight: 20kg
Binary inputs
Number: 10 (each fully isolated)
Modes:
Potential-free
Potential-sensing (automatic recognition)
Max measuring time: Infinite
Binary outputs
Number: 8
Type:
4 (1–4) relay contacts
4 (5–8) quick output contacts
Breaking capacity:
Vmax 250VAC / Imax 0.5A
Vmax 250VDC / Imax 0.3A
Auxiliary DC supply
Voltage: 110V / 220V (switch between)
Power: >100W
Power supply
Nominal input voltage: 175–260VAC
Nominal frequency: 50/60Hz