Working condition: -15℃~40℃; RH<80%
Anti-interference principle: Frequency conversion
Power supply: AC 85V~160V (Generator can be used)
High voltage output:
+ 0.5kV~12kV: Every 0.1kV
+ Precision: 2%
+ Maximum current: 200mA
+ Capacity: 2000VA
Self-excitation power: AC 0V~50V/15A
+ 45HZ/55HZ 47.5HZ/52.5HZ
+ 55HZ/65HZ 57.5HZ/62.5HZ
+ Automatic double frequency
Resolution: tgδ: 0.001%; Cx: 0.001pF
Accuracy: △tgδ:±(Reading*1.0%+0.040%); △Cx :±(Reading*1.0%+1.00PF)
Measurement range:
+ tgδ: Without limit
+ Cx: 15pF < Cx < 300nF
+ 12kV: Cx < 30 nF
+ 5kV: Cx < 150 nF
+ 1kV: Cx <300 nF
+ CVT test: Cx < 300 nF
CVT ratio range: 10~10000
CVT ratio accuracy: 0.1%
CVT ratio resolution: 0.01
Storage: 200 group supports U disk data storage
Dimension: Main unit: 350(L)×270(W)×270(H); Accessory box: 350(L)×270(W)×160(H)
Weight: Main unit: 22.75kg; Accessory box: 5.25kg
General Information:
EPJS-6000 is a new generation, fully automatic on-site measure dielectric loss(tgδ)and the capacitance (Cx) of electric equipment. It’s suitable for testing on transformer, insulating bush, capacitor, CT/PT, MOA etc.
Also called: Automatic Capacitance and Tan Delta Tester
Features:
-Build-in dielectric loss bridge, frequency conversion power supply, testing transformer, SF6 high stability standard capacitor.
-The test high-voltage source is generated by the inverter inside the instrument and is used for the test object after boosting the voltage from the transformer.
-Frequency can be changed into 50Hz, 47.5Hz/52.5Hz, 45Hz/55Hz, 60Hz, 57.5Hz/62.5Hz, 55Hz/65Hz. Digital notch technology is adopted to avoid the interference of power frequency electric field to the test.
-Multiple protection of input voltage fluctuation, output short circuit, over-voltage, over-current, temperature, secure and reliable. Meanwhile, it has the function of grounding testing, that voltage boost is not permitted for non-grounding equipment.
-LCD touch screen display. English menu easy to operate.
-200 groups’ data storage. Save testing result according to time order, check history record and print the result.
-Multiple testing mode, with modes of inside high voltage, outside high voltage, inner standard, external standard, GST/UST, self-excitation. High voltage (more than 12kV) dielectric loss test can be made in the situation of external standard outside high voltage.
-Test full sealed CVT (Capacitive Voltage Transformer) C1 and C2 dielectric loss and capacitance at the same time. Also test CVT transformation ratio and voltage angle difference.
-The instrument can accurately measure the CVT dielectric loss value and capacitance value without removing the CVT high voltage lead.
-The dielectric loss and capacitance value of C0 in the upper end of CVT can be measured by using the reverse shielding method.
-High speed sampling signal. Inverter and sampling circuit inside are digitized controlled. Output voltage is adjusted continuously.