Get exclusive volume discounts, bulk pricing updates, and new product alerts delivered directly to your inbox.
By subscribing, you agree to our Terms of Service and Privacy Policy.
Direct access to our certified experts
Get exclusive volume discounts, bulk pricing updates, and new product alerts delivered directly to your inbox.
By subscribing, you agree to our Terms of Service and Privacy Policy.
Direct access to our certified experts

Basic error and performance indicator under reference condition
Measuring range/Accuracy/Resolution
Earth Resistance(R)
0.00Ω~30.00Ω/±2%rdg±3dgt/0.01Ω
30.0Ω~300.0Ω/±2%rdg±3dgt/0.1Ω
300Ω~3000Ω/±2%rdg±3dgt/1Ω
3.00kΩ~30.00kΩ/±4%rdg±3dgt/10Ω
Soil Resistivity (ρ)
0.00Ωm~99.99Ωm/(ρ=2πaRa:1 m~100m;π=3.14)/0.01Ωm
100.0Ωm~999.9Ωm/(ρ=2πaRa:1 m~100m;π=3.14) /0.1Ωm
1000Ωm~9999Ωm/ (ρ=2πaRa:1 m~100m;π=3.14)/1Ωm
Soil Resistivity (ρ)
10.00kΩm~99.99kΩm/(ρ=2πaRa:1 m~100m;π=3.14)/10Ωm
100.0kΩm~999.9kΩm/ (ρ=2πaRa:1 m~100m;π=3.14)/100Ωm
1000kΩm~9000kΩm/(ρ=2πaRa:1 m~100m;π=3.14) /1kΩm
Earth Voltage
AC 0.0~600V/±2%rdg±3dgt/0.1V
General Specification
Power Supply: DC 7.4V 2600mAh rechargeable lithium battery, the battery is fully charged about 8.4V
Backlight: Controllable white screen backlight, suitable for use in dim place
Display Mode: 4-digit max LCD display, white screen backlight
Measurement Instruction: The LED flash during the measurement, the LCD count backward, and the progress bar chart indicate
LCD Display Domain: 124mm×67mm
Measurement Range
Earth resistance: 0.00Ω~30.00kΩ
Soil Resistivity: 0.00Ωm~9000kΩm
Earth Voltage: 0V~600V
Measurement: Precision four, three-wire measurement, simple two-wire measurement method to measure earth resistance
Measuring Method
Earth resistance: rated current transformer method, measuring current 20mA Max
Soil resistivity: quadru pole method (Wenner method)
Earth voltage: average rectification (between P(S)-ES interface)
Test Frequency: 128Hz/111Hz/105Hz/94Hz(AFC)
Test Current: >20mA(Sine wave)
Open Circuit Test Voltage: AC 40V max
Test Voltage Waveform: Sine wave
Electrode Spacing Range: Range can be set 1m~100m
Measurement Range Gear Shift
Earth Resistance: 0.00Ω~30.00kΩ Fully automatic shifting
Soil Resistivity: 0.00Ωm~9000kΩm Fully automatic shifting
Standard Test Line: 4 pieces: red 20m, black 20m, yellow 10m, green 10m each 1 piece
Simple Test Line: 2 pieces: red 1.6m, black 1.6m each 1 piece
Auxiliary Earth Rod: 4 pieces:φ9mm×230mm(about 935g)
Measurement Time
Earth voltage: about 3 times/second
Earth resistance, soil resistivity: about 15 seconds/time
Line Voltage: Measurement below AC 600V
Communication Interface: With USB interface, software monitoring, storage data can be uploaded to the computer, saved and printed
Communication Line: 1 USB communication line, 1.5m long
Memory: 300 groups, flashing "FULL”symbol indicates that the storage is full
Data Hold: Data holding function: “HOLD" symbol display
Data Access: Data access function: “READ" symbol display
Overflow Display: Over-range overflow function: “OL" symbol display
Interference Test: Automatically identify the interference signal, and the “NOISE” symbol indicates when the interference voltage is higher than 5V
Auxiliary Earth Test: With auxiliary earth resistance value test function,0.00KΩ~30kΩ(100R+rC<50kΩ,100R+rP<50kΩ)
Alarm Function: 300 groups, flashing "FULL”symbol indicates that the storage is full
Alarm Threshold Setting Range: Resistance:0Ω~9999Ω,voltage:0.0V~600.0V
Automatic Shutdown: Automatically shut down after 10 minutes of power on
Battery Voltage: When the battery voltage drop to about DC 7.2V±0.1V, the low battery voltage symbol is displayed to remind the meter that it need to be charged.
Working Current
Standby: about 20mA (backlight off)
Power on when turn on backlight: about 45mA (turn off the backlight 25mA)
Measurement: about 100mA (backlight off)
Tester Size: 280mm×260mm×160mm
Weight
Tester: About 2306g(include battery);total weight: about 6.3kg(include accessory)
Overload Protection: Measuring earth resistance: AC 280V/3 seconds between C(H)-E、P(S)-ES ports
Protection Level: IP65(closing)
Insulation Resistance: Above 20MΩ(500V between the circuit and the housing)
Withstand Voltage: AC 3700V/rms(Between the circuit and the housing)
Electromagnetic characteristics: IEC61326(EMC)
Suitable Safety Regulation: IEC61010-1(CAT Ⅲ 300V、CAT IV 150V、pollution level 2);IEC61010-031;IEC61557-1(Earth resistance);IEC61557-5(Soil resistivity);JJG 366-2004
Working Temperature & Humidity: -10℃~40℃; below 80%RH
Storage Temperature & Humidity: -20℃~60℃; below 70%RH