Operational Power Supply: AC220V±10%, 50Hz
Single Machine Output: 0~2500Vrms, 5kVA (maximum setting value 20A)
Primary Current Output: 0~1000A
Excitation accuracy: ≤0.5% (0.2%*reading+0.3%*range)
Secondary winding Resistance measurement:
Range: 0.1~300Ω
Accuracy: ≤0.5% (0.2%*reading+0.3%*range)
Secondary real Load measurement:
Range: 5~500VA
Accuracy: ≤0.5% (0.2%*reading+0.3%*range) ±0.1VA
Phase measurement (Angle difference):
Accuracy: 4min
Resolution: 0.1min
CT ratio measurement range:
Range: ≤25000A/5A(5000A/1A)
Accuracy: ≤0.5%
PT ratio measurement range:
Range: ≤500KV
Accuracy: ≤0.5%
Operating Temperature: -10ºC~+40ºC
Relative Humidity: <90RH%
Altitude: ≤1000m
Overall Dimension (Length×Width×Height): 410mm*260mm*340mm
Weight: ≤22 kg