Get exclusive volume discounts, bulk pricing updates, and new product alerts delivered directly to your inbox.
By subscribing, you agree to our Terms of Service and Privacy Policy.
Direct access to our certified experts
Get exclusive volume discounts, bulk pricing updates, and new product alerts delivered directly to your inbox.
By subscribing, you agree to our Terms of Service and Privacy Policy.
Direct access to our certified experts

Electrical parameters
Power Supply (AC/DC): AC85-400V / DC85-330V
Power consumption: <4VA
Measurement Parameters: Voltage (Ph-N); Voltage (Ph-Ph); Current; Frequency; PF;
Active Power(W); Reactive Power(Q); Apparent Power(S),
2nd to 49th harmonics(option)
Harmonics:
Total harmonics ratio of phase-voltage
Total harmonics ratio of current
2nd to 63st harmonics ratio of phase-voltage
2nd to 63st harmonics ratio of current
Maximum Value & Minimum Value: Voltage, current, frequency, active power, reactive power, apparent power,demandP,demandQ, demandS.
Computation:
Forward active power energy
Reverse active power energy
Forward active power energy
Reverse reactive power energy
Measuring Range: 0-800V, 0-10A, 45-65Hz, -1 ~ 0 ~ 1
Measuring Accuracy:
Voltage: 0.5%RD±0.05%FS
Current: 0.5%RD±0.05%FS
Active Power: 0.5%RD±0.05%FS
Reactive Power: 1.5%RD +0.05%FS
Apparent power: 0.5%RD +0.1%FS
Power Factor: 0.5%RD
Frequency: 0.05%RD
Active Energy: 0.5%
Maximum Demand: Ia, Ib, Ic, ΣPtotal, ΣQtotal, ΣStotal, 15 minutes
Display:
Blue back-lit LCD Display
5 display figures
4 operation keys
Communication:
Support RS-485 interface port, 32 (128) Networking
ModBus-TCP/IP SNMP communication protocol
Ethernet 10/100M port (RJ45)
Memory:
2M onboard memory,can be extended to 16M.
Data looger interval can set by end users from 1min to 60min.The default is 15min.
You can read the data through a PC, also you can select the data to diaplay and store from software.
Programmable:
Measuring system: 3P4W/3P3W etc
Transformation Ratio: PT 1-10000; CT 1-10000
Energy Pulse:
Provides active & reactive energy pulse output
Pulse parameters can be choosed
Range: 0.1-10000kWh/kvarh
Dry contact output (1Ax100V)
Connection Mode: 3P4W, 3P4W BAL, 3P3W, 3P3W BAL, 1P3W, 1P2W
Baud: 1200-57600, Standard 38400
Mechanical parameters
Dimensions (L x W x H) (mm): 96x96x12.8
Mounting: Panel mounting
Trepanning: 92x92mm
The thickness of installation: 51mm
Environmental conditions
Temperature: -5 to +50 °C
Humidity: 20%-95%RH, without condensation