DC Current range: 20.00 A/600.0 A, Basic accuracy: ±1.3% rdg. ±0.08 A (20 A range)
AC Current range: 20.00 A/600.0 A (10 Hz to 1 kHz, True RMS), Basic accuracy: 45-66 Hz: ±1.3% rdg. ±0.08 A (at 20 A)
Crest factor: 20.00 A range: 7.5
600.0 A range: 3 or less
DC+AC Current range: 20.00 A/600.0 A (10 Hz to 1 kHz, True RMS), Basic accuracy DC, 45-66 Hz: ±1.3% rdg. ±0.13 A (at 20 A)
DC Voltage range: 600.0 mV to 1000 V (When using P2000: 600.0 V to 2000 V)
AC Voltage range: 6.000 V to 1000 V, 4 ranges (15 Hz to 1 kHz, True RMS), Basic accuracy 45 - 66 Hz: ±0.9% rdg. ±0.003 V (at 6 V)
DC+AC Voltage range: 6.000 V to 1000 V, 4 ranges, Basic accuracy DC, 45 - 66 Hz: ±1.0% rdg. ±0.013 V (at 6 V)
Resistance range: 600.0 Ω to 6.000 MΩ, 5 ranges, Basic accuracy: ±0.7% rdg. ±0.5 Ω (at 600 Ω)
Capacitance range: 1.000 μF to 1000 μF, 4 ranges, Basic accuracy: ±1.9% rdg. ±0.005 μF (at 1 μF)
Frequency range: 9.999 Hz to 999.9 Hz, 3 ranges, Basic accuracy: ±0.1% rdg. ±0.003 Hz (at 9.999 Hz)
Voltage detection: Hi: 40 V to 600 V AC, Lo: 80 V to 600 V AC, 50/60 Hz
Harmonic levels: [With Z3210 installed] Voltage/Current harmonic levels up to 30th, Content factor, Total harmonic distortion ratio
*Harmonics can be displayed with our free app GENNECT Cross.
Other functions: DC power, Continuity check, Diode check, Automatic AC/DC detection, Pass/fail judgement function of DC A and DC V, Max/Min/Average/PEAK MAX/ PEAK MIN value display, Low-pass filter function, Display value hold, Auto hold, Back light, Auto-power save, Buzzer sounds, Zero-adjustment
Dustproof, waterproof: IP54
Power supply: LR03 Alkaline battery ×2
Continuous use: 40 hr (without Z3210 installed), 20 hr. (with Z3210 installed and using wireless communications)
Other conditions: 10 A AC measurement, backlight off, 23°C reference value
Core jaw diameter: φ33 mm (1.30 in), Jaw dimension: 69 mm (2.72 in) W× 14 mm (0.55 in) D
Dimensions and mass: 65 mm (2.56 in) W × 215 mm (8.46 in) H × 35 mm (1.38 in) D mm, 340 g (12.0 oz)