Measurement ranges:
+ CO2: 0–2000 ppm / 400–2000 ppm (selectable via jumper)
+ VOC: CO₂eq: 400–2000 ppm; TVOC ppm: 0–30.0 ppm; TVOC µg/m3: 0–10000 µg/m3; IAQ index: 1–5 (UBA rating)
+ PM1/PM2.5/PM10: 0–50 μg/m³ / 0–500 μg/m³ (selectable via jumper); IAQ index: 1-5 (WHO rating)
+ Temperature: 0...50 °C
+ Relative humidity: 0–100 %rH
Communication: RS-485 Modbus (RTU)
Accuracy:
+ CO₂: ±40 ppm + 3 % of reading (typical), additional ±60 ppm for first weeks
+ Relative humidity: ±2.2 % rH (typical at 20 °C, 30 % rH)
+ Temperature: ±0.4 °C (typical at 20 °C)
+ VOC: ±15 % of reading (typical)
*VOC sensor is tuned for typical IAQ Mix of 22 VOCs as defined by Mølhave et al. (1997)
+ PM:
0…100 μg/m3:
PM2.5: ±15 μg/m3(at 25 ⁰C ±5 ⁰C)
PM1/PM10*: ±25 μg/m3 (at 25 ⁰C ±5 ⁰C)
100…1000 μg/m3:
PM2.5: ±15 % (at 25 ⁰C ±5 ⁰C)
PM1/PM10*: ±25 % (at 25 ⁰C ±5 ⁰C)
*PM1 and PM10 values are calculated from PM2.5 measurement reading with the default particle distribution.
Measuring elements:
+ CO2: Non-dispersive infrared (NDIR)
+ VOC: Complementary Metal Oxide Semiconductor (CMOS)
+ PM: Laser-based light scattering particle sensing
+ Temperature: Integrated to CMOS
+ Relative humidity: Thermoset polymer capacitive sensing element
Measuring units:
+ CO2: ppm
+ Relative humidity: % rH
+ Temperature: °C
+ VOC CO2eq: ppm
+ TVOC: ppm, μg/m3
+ PM1/2.5/10: μg/m3
Calibration (CO2): Automatic self-calibration, ABC LogicTM
Supply voltage: 24 VDC/VAC ±10 %
Output signal 1–4: 0...10 V (optional 2...10 V / 0...5 V, display or configuration tool required); Optional 4...20 mA
Linear to selected measurement (CO2, VOC, PM, rH or Temp)
Operating temperature: 0...50 °C
Protection standard: IP20
Noted:
CO2 = Carbon dioxide sensor