- Voltage (RCD, LOOP, Phase sequence):15~ 460V
- Frequency: 47.0~63.6 Hz
- Continuity test on protective and equalizing conductors: 0.01 ~99.9Ω
- Insulation resistance (DC voltage): 50, 100, 250, 500, 1000V; Range: 0.01~1999MΩ
- Z Line (Line-Line, Line-Neutral, Line-PE):0.00~199.9Ω
- First fault current (IT systems): 0.1~999mA
- RCD test (Molded case type)
RCD type: AC, A, B – General (G), Selective (S) and Delayed ( )
Rated tripping currents(IΔN): 10mA, 30mA, 100mA, 300mA, 500mA, 650mA, 1000mA
Line-PE, Line-N voltage: 100V~265V RCD type AC and A, 190V~265V RCD type B
Frequency: 50/60Hz ± 5%
- RCD tripping current: Type AC, A,B; (0.3~1.1) IΔN
RCD Molded type tripping time range [ms] (TT/TN system): 10mA; 30mA; 100mA;300mA;500mA; 650mA; 1000mA
RCD Molded type tripping time range [ms] (IT system): 10mA; 30mA; 100mA;300mA;500mA; 650mA; 1000mA
- Test on earth leakage delay tester RCDs (with RCDX10 optional accessory)
RCD type: AC, A , B – General (G), Selective (S) and Delayed ( )
Rated tripping currents (IΔN): 0.3A~10A
Line-PE, Line-N voltage: 100V~265V RCD type AC and A, 190V~265V RCD type B
Frequency: 50/60Hz±5%
- Earth leakage delay tester RCDs tripping current (RCD General): RCD Type: AC, A,B; (0.3~1.1) IΔN
- Earth leakage delay tester RCDs trip out time range [ms] (TT/TN system): 0.3A+1.0A; 1.1A+3.0A; 3.1A+ 6.5A, 6.6A+10.0A
- Earth leakage delay tester RCDs trip out time range [ms] (IT system): 0.3A+1.0A; 1.1A+3.0A; 3.1A+ 6.5A, 6.6A+10.0A
- RA – Non-trip earth loop impedance: 100~265V (Line-PE)
- RA – Systems with Neutral wire:1~1999 Ω
- Contact voltage (RCD and Ra test): 0~Utlim
- Contact voltage (EARTH test – TT system): 0 ~ 99.9V
- Contact voltage (EARTH test – TN system): 0 ~ 999V
- Ground resistance with 3-wire method: 0.01Ω ~ 49.99kΩ
- Soil resistivity with 4-wire Wenner method: 0.06Ωm~3.14MΩ
- Phase sequence rotation with 1-wire method: 100 ~ 265V
- Voltage drop on main power lines (ΔV%): 0~100%
- Leakage current (by HT96U optional clamp transducer):
1; 0.1mA
10 1 < FS <10; 0.01A
10≤ FS <300; 0.1A
300 ≤ FS <3000; 1A
- Environmental parameters (AUX function):
+ Temperature [°C]: -20°C ~ 80°C 0.1 °C
+ Temperature [°F]: -4°F ~ 176°F; 0.1 °F
+ Relative humidity [%HR]: 0 ~ 100%HR; 0.1% UR
+ DC output voltage: 0.1mV ~ 1.0V; 0.1mV
+ Illuminance [Lux] (Optional)
0.001Lux ~ 20.00 Lux; 0.001~0.02 Lux
0.1 Lux ~ 2000 Lux; 0.1 ~ 2 Lux
1 Lux ~ 20 kLux ; 1 ~ 20 Lux
- AC TRMS Voltage (Phase-Neutral): 15.0 ~ 380.0V
- AC TRMS Voltage (Phase-Phase): 15.0 ~ 660.0V
- Frequency: DC, 42 ~ 69.0 Hz
- DC/ AC TRMS Current (STD clamp):
≤ 10A: 5% FS ~9.99
10A ≤ FS ≤ 300: 5% FS ~ 299.9
300A ≤ FS ≤ 3000: 5% FS ~ 2999
- AC TRMS Current (FLEX clamp – 300A AC): 0.085~85.0mV
- AC TRMS Current (FLEX clamp – 3000A AC): 0.425 ~ 255.0mV
- DC Power: 0~9999kW
- Active power: 0~9999kW
- Reactive Power: 0~9999kW
- Power factor/ Cos φ: 0.70c ÷ 1.00 ÷ 0.70i
- Voltage harmonics: 0.1 ~ 100.0%
- Current harmonics: 0.1 ~ 100.0%
- Voltage anomalies (Phase-Neutral, Phase-PE): 15.0 ~ 380V
- Voltage anomalies (Phase- Phase): 15.0 ~ 660V
Included Accessories
HTFLEX33E AC flexible clamp for currents up to 3000A, diameter 174mm, 4 pcs
C2033X 3-banana to Shuko plug cable
UNIVERSALKITG3 Set of 4 cables, 4 alligator clips and 3 test leads
KITTERRNE Soft carrying bag containing 4 cables and 4 earth rods
PR400 Remote switch probe
PT400 Stylus
BORSA2051 Soft carrying bag
TOPVIEW2006 PC software and optical-to-USB connection cable C2006
YABAT0003000 Rechargeable NiMH battery 1.2V, AA, 6 pcs
A0060 Power Supplier\Battery Charger 100/230Vac - 15Vdc, 10W CAT IV
C7051 Power cable Shuko-Europlug ground-less 1.50mt
SP-5100 Hands Free kit
Quick user’s guide
User’s manual on CD-ROM
Calibration certificate ISO9000