Impulse voltage grade: 100kV-7200kV
Standard lightning wave: 1.2±30%/50±20%µS
Peak oscillation: <5%
Standard switching wave: 250±20%/2500±60%µS
Virtual front time of oscillating lightning wave: ≤15µS
Virtual front time of oscillating switching wave and virtual front time of oscillating switching impulse wave: 15µS-1mS
The minimum output voltage: ≥10%Un
Charging voltage instability: <±1%
Synchronizing range: ≥20%
Synchronous discharge error rate: <2%
Ignition range: 10%~100%
Working time:
≥70%UN Discontinuous work (charge-discharge 300s/time)
<70%nn Continuous work (charge-discharge 120s/time)
Generator efficiency: lightning wave (no load): ≥90%
Time to chopping: 2~5µS