Get exclusive volume discounts, bulk pricing updates, and new product alerts delivered directly to your inbox.
By subscribing, you agree to our Terms of Service and Privacy Policy.
Direct access to our certified experts
Get exclusive volume discounts, bulk pricing updates, and new product alerts delivered directly to your inbox.
By subscribing, you agree to our Terms of Service and Privacy Policy.
Direct access to our certified experts

Voltage generators
Range
4-phase AC 4 x 300 V
4-channel DC 4 x 300 V
Power
4-phase AC 4 x 125 VA (max)
4-channel DC 4 x 125 W (max)
Inaccuracy AC
Typical 0.03% of reading + 0.01% of range
Guaranteed 0.05% of reading + 0.03% of range
Distortion(THD+N) 1) < 0.14% typical (0.25% max)
Resolution 10 mV
Phase
Angle range 0º - 360º
Inaccuracy 2) < 0.5º (at 50 and 60 Hz)
Resolution 0.1º
Frequency
Range 10 Hz - 600 Hz
Inaccuracy 2) <0.03 % (45 Hz - 66 Hz)
Resolution 1 mHz
Current generators
Range
3-phase AC 3 x 35 A
At least 15 repetitions: 10 s ON and 20
s OFF
3-phase DC 3 x 35 A
At least 15 repetitions: 10 s ON and 20
s OFF
3-phase AC 3 x 20 A continuous
3-phase DC 3 x 20 A continuous
Power
3-phase AC (max) 3 x 277 VA
3-phase DC (max) 3 x 275 W
Included accessories
Test cable set standard GA-00030
Earth (ground) cable GA-00200
Cable set 900 V GA-00036
Flight case with wheels GD-00185
Instrument configuration
Main Prefault - Fault
Ramping Sequencer CT Magnetization
Impedance
Prefault - Fault with MTT
Prefault - Fault
with MTT and
reference curves