For full functionality of this site it is necessary to enable JavaScript.
EMIN.VN
0
Product image

Megger TORKEL 930 Battery Discharge Test System (0 - 220 A)

Contact
Secure Checkout
Quality Engagement
Easy change and return
Delivery Available

Environment

Application field: The instrument is intended for use in high-voltage

substations and industrial environments.

Temperature

Operating: 0°C to +50°C (32°F to +122°F) Power derating at temperatures over +35°C(+95°F)

Storage & transport: -40°C to +70°C (-40°F to +158°F)

Humidity: 5% – 95% RH, non-condensing

Shock/Vibration/Fall

Instrument only: ETSI EN 300 019-2-7 class 7M2

Instrument in transport case: ISTA 2A

Altitude

Operating: 3,000 m (10,000 ft)

Storage: 10,000 m (33,000 ft)

Encapsulation class: IP20


CE-marking

LVD: 2014/35/EU

EMC: 2014/30/EU

RoHS: 2011/65/EU


General

Mains voltage: 100 – 240 V AC, 50/60 Hz

Power consumption: 200 W (max)

Power interruption: 40 ms (max)

Protection: Thermal cut-outs, Automatic overload protection, Emergency stop button

Dimensions: 519x315x375 mm, (20.5”x12.4”x14.7”)

Weight:

19.5 kg (43.0 lbs) instrument

31.9 kg (70.3 lbs) incl. standard transport case

39.2 kg (86.4 lbs) incl. large transport case and cables

Display: 7" LCD, Capacitive touch screen

Available languages: Czech, English, French, German, Romanian, Russian, Spanish, Swedish

Number of test files: 30 (max)

Test time: 240 h (max)


Measurement section

Current measurement

Display range: 0.0 to 2999.0 A

Basic inaccuracy: ±(0.5% of reading +0.1 A)

Resolution: 0.1 A

Internal current measurement

Range: 0 to 220 A

Input for clamp-on probe

Range: 0 to 1000 mV DC

mV/A-ratio: 0.30 mV/A to 100.00 mV/A

Input impedance: >1 MΩ

Voltage measurement

Voltage: 0 to 500 V DC

Inaccuracy: ±(0.5% of reading +0.1 V DC)

Resolution: 0.1 V

Sample rate: 10 Hz, Values are saved when change is >10mV

Time measurement

Inaccuracy: ±0.1% of reading ±1 digit


Load section

Battery voltage: 7.5 V3) to 300 V1) / 500 V2)

Power: 15 kW (max)

Load patterns: Constant current, constant power, constant

resistance, current or power profile

Constant I

Range: 0 to 220.0 A

Inaccuracy: ±(0.5% +0.2 A)

Resolution: 0.1 A

Ripple: max 0.5 A peak

Constant R

Range: 300 mΩ to 3 kΩ

Inaccuracy: ±1% typical

Resolution: 100 mΩ

Constant P

Range: 0 to 15 kW

Inaccuracy: ±1% typical

Resolution: 10 W


Inputs

+: 7.5 to 300 V.1) 7.5 to 500 V.2)

–: 0 V

I EXT ≤ 1 V: 1 V DC, 300 V DC to ground

VOLTAGE SENSE: Impedance to the current terminals is >1 MΩ


Outputs

ALARM Relay contact: 28 V DC, 8 A, 240 V AC, 8 A. Devices higher than Cat II must not be attached

TXL STOP Relay contact: 250VDC, 0.28A, 28VDC, 8A, 250VAC, 8A

9 V DC: 9 V DC, ±7% max 100 mA

Datasheet

Stay Updated with Offers

Get exclusive volume discounts, bulk pricing updates, and new product alerts delivered directly to your inbox.

By subscribing, you agree to our Terms of Service and Privacy Policy.

Quick Support

Direct access to our certified experts