Megger TORKEL 950 Battery Discharge Test System (0 - 220 A)
Environment
Application field: The instrument is intended for use in high-voltage
substations and industrial environments.
Temperature
Operating: 0°C to +50°C (32°F to +122°F) Power derating at temperatures over +35°C(+95°F)
Storage & transport: -40°C to +70°C (-40°F to +158°F)
Humidity: 5% – 95% RH, non-condensing
Shock/Vibration/Fall
Instrument only: ETSI EN 300 019-2-7 class 7M2
Instrument in transport case: ISTA 2A
Altitude
Operating: 3,000 m (10,000 ft)
Storage: 10,000 m (33,000 ft)
Encapsulation class: IP20
CE-marking
LVD: 2014/35/EU
EMC: 2014/30/EU
RoHS: 2011/65/EU
General
Mains voltage: 100 – 240 V AC, 50/60 Hz
Power consumption: 200 W (max)
Power interruption: 40 ms (max)
Protection: Thermal cut-outs, Automatic overload protection, Emergency stop button
Dimensions: 519x315x375 mm, (20.5”x12.4”x14.7”)
Weight:
19.5 kg (43.0 lbs) instrument
31.9 kg (70.3 lbs) incl. standard transport case
39.2 kg (86.4 lbs) incl. large transport case and cables
Display: 7" LCD, Capacitive touch screen
Available languages: Czech, English, French, German, Romanian, Russian, Spanish, Swedish
Number of test files: 30 (max)
Test time: 240 h (max)
Measurement section
Current measurement
Display range: 0.0 to 2999.0 A
Basic inaccuracy: ±(0.5% of reading +0.1 A)
Resolution: 0.1 A
Internal current measurement
Range: 0 to 220 A
Input for clamp-on probe
Range: 0 to 1,000 mV DC
mV/A-ratio: 0.30 mV/A to 100.00 mV/A
Input impedance: >1 MΩ
Voltage measurement
Voltage: 0 to 500 V DC
Inaccuracy: ±(0.5% of reading +0.1 V DC)
Resolution: 0.1 V
Sample rate: 10 Hz, Values are saved when change is >10mV
Time measurement
Inaccuracy: ±0.1% of reading ±1 digit
Load section
Battery voltage: 7.5 V3) to 300 V1) / 500 V2)
Power: 15 kW (max)
Load patterns: Constant current, constant power, constant
resistance, current or power profile
Constant I
Range: 0 to 220.0 A
Inaccuracy: ±(0.5% +0.2 A)
Resolution: 0.1 A
Ripple: max 0.5 A peak
Constant R
Range: 300 mΩ to 3 kΩ
Inaccuracy: ±1% typical
Resolution: 100 mΩ
Constant P
Range: 0 to 15 kW
Inaccuracy: ±1% typical
Resolution: 10 W
Inputs
+: 7.5 to 300 V.1) 7.5 to 500 V.2)
–: 0 V
I EXT ≤ 1 V: 1 V DC, 300 V DC to ground
VOLTAGE SENSE: Impedance to the current terminals is >1 MΩ
Outputs
ALARM Relay contact: 28 V DC, 8 A, 240 V AC, 8 A. Devices higher than Cat II must not be attached
TXL STOP Relay contact: 250VDC, 0.28A, 28VDC, 8A, 250VAC, 8A
9 V DC: 9 V DC, ±7% max 100 mA