Metrel MI 3121H Standard set Insulation/Continuity Tester (100 GΩ; 100 ~ 2500 V)
Insulation resistance (test voltages 100 VDC and 250 VDC) (Measuring range/Resolution/Accuracy) :
0.00 ... 19.99 MΩ / 0.01 MΩ / ±(5 % of reading + 3 digits)
20.0 ... 199.9 MΩ / 0.1 MΩ / ±10 % of reading
200 ... 999 MΩ / 1 MΩ / ±20 % of reading
Insulation resistance (test voltages 500 VDC, 1000 VDC and 2500 VDC) (Measuring range/Resolution/Accuracy):
0.00 MΩ ... 19.99 MΩ / 0.01 MΩ / ±(5 % of reading + 3 digits)
20.0 MΩ ... 199.9 MΩ / 0.1 MΩ / ±5 % of reading
200 MΩ ... 999 MΩ / 1 MΩ / ±5 % of reading
1.00 GΩ ... 4.99 GΩ / 10 MΩ / ±10 % of reading
5.00 GΩ ... 19.99 GΩ / 10 MΩ / ±20 % of reading
20.0 GΩ ... 99.9 GΩ / 100 MΩ / ±20 % of reading
Internal Test Voltage Readback (Measuring range/Resolution/Accuracy):
0 V ... 1999 V / 1 V / ±(3 % of reading + 3 digits)
2.00 kV ... 3.00 kV / 10 V / ±3 % of reading
Dielectric absorption ratio DAR, Polarization index PI (Measuring range/Resolution/Accuracy):
0.01 ... 9.99 / 0.01 / ±(5 % of reading + 2 digits)
10.0 ... 100.0 / 0.1 / ±5 % of reading
Continuity (200 mA) (Measuring range/Resolution/Accuracy):
0.00 ... 19.99 Ω / 0.01 Ω / ±(3 % of reading + 3 digits)
20.0 ... 199.9 Ω / 0.1 Ω / ±5 % of reading
200 ... 1999 Ω / 1 Ω / ±10 % of reading
Open-circuit voltage: 6.5 VDC ... 9 VDC
Measuring current: min. 200 mA into 2 Ω load
Continuity (7 mA) (Measuring range/Resolution/Accuracy):
0.0 ... 19.9 Ω / 0.1 Ω / ±(5 % of reading + 3 digits)
20 ... 1999 Ω / 1 Ω / ±10 % of reading
Voltage (True RMS) (Measuring range/Resolution/Accuracy):
0.00 ... 9.99 V / 0.01 V / ±(3 % of reading + 3 digits)
10.0 ... 99.9 V / 0.1 V / ±(3 % of reading + 3 digits)
100 ... 550 V / 1 V / ±(3 % of reading + 3 digits)
Nominal frequency range: 0 Hz, 15 Hz ... 500 Hz
Frequency (Measuring range/Resolution/Accuracy):
0.00 ... 19.99 Hz / 0.01 Hz / ±(0.2 % of reading + 1 digit)
20.0 ... 199.9 Hz / 0.1 Hz / ±(0.2 % of reading + 1 digit)
200 ... 500 Hz / 1 Hz / ±(0.2 % of reading + 1 digit)
Power supply: 6 x 1.5 V batteries or rechargeable batteries, size AA
Overvoltage category: CAT III / 600 V; CAT IV / 300 V
Protection classification: double insulation
Pollution degree: 2
Protection degree: IP 40
Display: custom liquid crystal display with backlight
Memory: 1900 measurements
Dimensions (w x h x d): 14 cm x 8 cm x 23 cm
Weight (without batteries): 0.85 kg
• Instrument SMATREC 2,5 kV Insulation / Continuity
• Soft hand strap
• Test lead, 2 x 1.5 m
• Test probes, 2 pcs (black, red)
• Crocodil clips, 2 pcs (black, red)
• Power supply adapter + 6 NiMH rechargeable batteries, size AA
• Instruction manual on CD
• Short instruction manual
• Handbook “Guide for testing and verification of low voltage installations” on CD
Get exclusive volume discounts, bulk pricing updates, and new product alerts delivered directly to your inbox.
By subscribing, you agree to our Terms of Service and Privacy Policy.
Direct access to our certified experts