Metrel MI 3136 Basic set Multifunctional Electrical Installation Tester (50 V ~ 1000 V)
Continuity (Measuring range/ Resolution/ Accuracy)
Test Current 8.5 mA 2-wire:
0.0 Ω ... 19.99 Ω / 0.1 Ω / ±(5 % of reading + 3 digits)
20 Ω ... 1999 Ω / 1 Ω / ±(5 % of reading + 3 digits)
Test Current 200 mA 2-wire:
0.00 Ω ... 19.99 Ω / 0.01 Ω / ±(3 % of reading + 3 digits)
20.0 Ω ... 199.9 Ω / 0.1 Ω / ±(5 % of reading)
200.0 Ω ... 1999 Ω / 1 Ω / ±(5 % of reading)
Rpe (RCD: No):
0.00 Ω ... 19.99 Ω / 0.01 Ω / ±(5 % of reading + 5 digits)
20.0 Ω ... 199.9 Ω / 0.1 Ω / ±(5 % of reading + 5 digits)
200 Ω ... 1999 Ω / 1 Ω / ±(5 % of reading + 5 digits)
Insulation Resistance (Measuring range/ Resolution/ Accuracy)
Test Voltage 50/100/250 V:
0.00 MΩ ... 19.99 MΩ / 0.01 MΩ / ±(5 % of reading + 3 digits)
20.0 MΩ ... 99.9 MΩ / 0.1 MΩ / ±(10 % of reading)
100.0 MΩ ... 199.9 MΩ / 0.1 MΩ / ±(20 % of reading)
Test Voltage 500 V:
0.00 MΩ ... 19.99 MΩ / 0.01 MΩ / ±(5 % of reading + 3 digits)
20.0 MΩ ... 199.9 MΩ / 0.1 MΩ / ±(5 % of reading)
200 MΩ ... 999 MΩ / 1 MΩ / ±(10 % of reading)
Test Voltage 1000 V:
0.00 MΩ ... 19.99 MΩ / 0.01 MΩ / ±(5 % of reading + 3 digits)
20.0 MΩ ... 199.9 MΩ / 0.1 MΩ / ±(5 % of reading)
Voltage (Um): 0 V ... 1200 V / 1 V / ±(3 % of reading + 3 digits)
RCD Test (Measuring range/ Resolution/ Accuracy)
RCD Uc (Contact Voltage):
0.0 V ... 19.9 V / 0.1 V / (-0 %/+15 %) of reading ± 10 digits
20.0 V ... 99.9 V / 0.1 V / (-0 %/+15 %) of reading
RCD (t) (Trip Time):
0.0 ms ... 40.0 ms / 0.1 ms / ±1 ms
40.1 ms ... 999.9 ms / 0.1 ms / ±3 ms
1000 ms ... 1999 ms / 1 ms / ±3 ms
2.00 s ... 10.00 s / 10 ms / ±10 ms
RCD I Ramp (Trip Current):
0.1 mA ... 1.10 A / (Range dependent) / ±10 %
Impedance (Measuring range/ Resolution/ Accuracy)
Zline (L-L, L-N) & Zloop (L-PE):
0.00 Ω ... 9.99 Ω / 0.01 Ω / ±(3 % of reading + 3 digits)
10.0 Ω ... 99.9 Ω / 0.1 Ω / ±(3 % of reading + 3 digits)
100 Ω ... 999 Ω / 1 Ω / ±(10 % of reading)
1.00 kΩ ... 9.99 kΩ / 10 Ω / ±(10 % of reading)
Zs RCD:
0.00 Ω ... 9.99 Ω / 0.01 Ω / ±(5 % of reading + 10 digits)
10.0 Ω ... 99.9 Ω / 0.1 Ω / ±(5 % of reading + 10 digits)
100 Ω ... 9.99 kΩ / 1 Ω ... 10 Ω / ±(10 % of reading)
Voltage & Frequency (Measuring range/ Resolution/ Accuracy)
Voltage: 0 V … 550 V / 1 V / ±(2 % of reading + 2 digits)
Frequency: 14.0 Hz ... 499.9 Hz / 0.1 Hz / ±(0.2 % of reading + 1 digit)
EARTH RESISTANCE (Measuring range/ Resolution/ Accuracy)
3-wire Method:
0.00 Ω ... 19.99 Ω / 0.01 Ω / ±(5 % of reading + 5 digits)
20.0 Ω ... 199.9 Ω / 0.1 Ω / ±(5 % of reading + 5 digits)
200.0 Ω ... 9999 Ω / 1 Ω / ±(5 % of reading + 5 digits)
General Data
Power Supply: 7.2 V (5200 mAh) Li-ion battery pack
Overvoltage Category: 600 V CAT III; 300 V CAT IV
Protection Class: Double insulation
COM Port: Bluetooth, USB Type-C
Display: 4.3 inch Colour TFT touch screen (480 x 272 pixels)
Weight: 1.35 kg
Dimensions (L x H x W): 272 x 152 x 70 mm
Standard set (ST)
• Instrument MI 3136 EurotestCOMBO XC
• 1x A 1014 Test probe, Black
• 1x A 1015 Test probe, Blue
• 1x A 1062 Test probe, Green
• 1x A 1013 Crocodile clip, Black
• 1x A 1310 Crocodile clip, Blue
• 1x A 1309 Crocodile clip, Green
• 1x A 1193 Test cable, BLK/GRN/BLU, 1.5m,
0.75mm2
• 1x A 1053 Test cable, 1.5m, 0.75mm2
• 1x A 1857 USB cable, Type C
• Calibration certificate
• Short instruction manual
• Instruction manual
• Metrel ES Manager BASIC Licence
• SW 1201 Metrel ES Manager (program installation)
Get exclusive volume discounts, bulk pricing updates, and new product alerts delivered directly to your inbox.
By subscribing, you agree to our Terms of Service and Privacy Policy.
Direct access to our certified experts