Metrel MI 3136 Multifunctional Electrical Installation Tester (50 V ~ 1000 V)
Continuity (Measuring range/ Resolution/ Accuracy)
Test Current 8.5 mA 2-wire:
0.0 Ω ... 19.99 Ω / 0.1 Ω / ±(5 % of reading + 3 digits)
20 Ω ... 1999 Ω / 1 Ω / ±(5 % of reading + 3 digits)
Test Current 200 mA 2-wire:
0.00 Ω ... 19.99 Ω / 0.01 Ω / ±(3 % of reading + 3 digits)
20.0 Ω ... 199.9 Ω / 0.1 Ω / ±(5 % of reading)
200.0 Ω ... 1999 Ω / 1 Ω / ±(5 % of reading)
Rpe (RCD: No):
0.00 Ω ... 19.99 Ω / 0.01 Ω / ±(5 % of reading + 5 digits)
20.0 Ω ... 199.9 Ω / 0.1 Ω / ±(5 % of reading + 5 digits)
200 Ω ... 1999 Ω / 1 Ω / ±(5 % of reading + 5 digits)
Insulation Resistance (Measuring range/ Resolution/ Accuracy)
Test Voltage 50/100/250 V:
0.00 MΩ ... 19.99 MΩ / 0.01 MΩ / ±(5 % of reading + 3 digits)
20.0 MΩ ... 99.9 MΩ / 0.1 MΩ / ±(10 % of reading)
100.0 MΩ ... 199.9 MΩ / 0.1 MΩ / ±(20 % of reading)
Test Voltage 500 V:
0.00 MΩ ... 19.99 MΩ / 0.01 MΩ / ±(5 % of reading + 3 digits)
20.0 MΩ ... 199.9 MΩ / 0.1 MΩ / ±(5 % of reading)
200 MΩ ... 999 MΩ / 1 MΩ / ±(10 % of reading)
Test Voltage 1000 V:
0.00 MΩ ... 19.99 MΩ / 0.01 MΩ / ±(5 % of reading + 3 digits)
20.0 MΩ ... 199.9 MΩ / 0.1 MΩ / ±(5 % of reading)
Voltage (Um): 0 V ... 1200 V / 1 V / ±(3 % of reading + 3 digits)
RCD Test (Measuring range/ Resolution/ Accuracy)
RCD Uc (Contact Voltage):
0.0 V ... 19.9 V / 0.1 V / (-0 %/+15 %) of reading ± 10 digits
20.0 V ... 99.9 V / 0.1 V / (-0 %/+15 %) of reading
RCD (t) (Trip Time):
0.0 ms ... 40.0 ms / 0.1 ms / ±1 ms
40.1 ms ... 999.9 ms / 0.1 ms / ±3 ms
1000 ms ... 1999 ms / 1 ms / ±3 ms
2.00 s ... 10.00 s / 10 ms / ±10 ms
RCD I Ramp (Trip Current):
0.1 mA ... 1.10 A / (Range dependent) / ±10 %
Impedance (Measuring range/ Resolution/ Accuracy)
Zline (L-L, L-N) & Zloop (L-PE):
0.00 Ω ... 9.99 Ω / 0.01 Ω / ±(3 % of reading + 3 digits)
10.0 Ω ... 99.9 Ω / 0.1 Ω / ±(3 % of reading + 3 digits)
100 Ω ... 999 Ω / 1 Ω / ±(10 % of reading)
1.00 kΩ ... 9.99 kΩ / 10 Ω / ±(10 % of reading)
Zs RCD:
0.00 Ω ... 9.99 Ω / 0.01 Ω / ±(5 % of reading + 10 digits)
10.0 Ω ... 99.9 Ω / 0.1 Ω / ±(5 % of reading + 10 digits)
100 Ω ... 9.99 kΩ / 1 Ω ... 10 Ω / ±(10 % of reading)
Voltage & Frequency (Measuring range/ Resolution/ Accuracy)
Voltage: 0 V … 550 V / 1 V / ±(2 % of reading + 2 digits)
Frequency: 14.0 Hz ... 499.9 Hz / 0.1 Hz / ±(0.2 % of reading + 1 digit)
EARTH RESISTANCE (Measuring range/ Resolution/ Accuracy)
3-wire Method:
0.00 Ω ... 19.99 Ω / 0.01 Ω / ±(5 % of reading + 5 digits)
20.0 Ω ... 199.9 Ω / 0.1 Ω / ±(5 % of reading + 5 digits)
200.0 Ω ... 9999 Ω / 1 Ω / ±(5 % of reading + 5 digits)
General Data
Power Supply: 7.2 V (5200 mAh) Li-ion battery pack
Overvoltage Category: 600 V CAT III; 300 V CAT IV
Protection Class: Double insulation
COM Port: Bluetooth, USB Type-C
Display: 4.3 inch Colour TFT touch screen (480 x 272 pixels)
Weight: 1.35 kg
Dimensions (L x H x W): 272 x 152 x 70 mm