For full functionality of this site it is necessary to enable JavaScript.
EMIN.VN
0
Product image

Metrel MI 3152H Standard set Multifunctional Electrical Installation Tester (50 V ~ 2500 V)

ModelMI 3152H Standard set
Contact
Secure Checkout
Quality Engagement
Easy change and return
Delivery Available

Continuity (Measuring range/ Resolution/ Accuracy)

Test Current 7 mA 2-wire:

0.00 Ω ... 19.99 Ω / 0.1 Ω / ±(5 % of r. + 3 digits)

20.0 Ω ... 1999 Ω / 1 Ω / ±(5 % of r. + 3 digits)

Test Current 200 mA 2-wire:

0.00 Ω ... 19.99 Ω / 0.01 Ω / ±(3 % of r. + 3 digits)

20.0 Ω ... 199.9 Ω / 0.1 Ω / ±(5 % of r.)

200.0 Ω ... 1999 Ω / 1 Ω / ±(5 % of r.)

Insulation Resistance (Measuring range/ Resolution/ Accuracy)

Test Voltage 50/100/250 V:

0.00 MΩ ... 19.99 MΩ / 0.01 MΩ / ±(5 % of r. + 3 digits)

20.0 MΩ ... 99.9 MΩ / 0.1 MΩ / ±(10 % of r.)

100.0 MΩ ... 199.9 MΩ / 0.1 MΩ / ±(20 % of r.)

Test Voltage 500/1000 V:

0.00 MΩ ... 19.99 MΩ / 0.01 MΩ / ±(5 % of r. + 3 digits)

20.0 MΩ ... 199.9 MΩ / 0.1 MΩ / ±(5 % of r.)

200 MΩ ... 999 MΩ / 1 MΩ / ±(10 % of r.)

Test Voltage 2500 V:

0.00 MΩ ... 19.99 MΩ / 0.01 MΩ / ±(5 % of r. + 3 digits)

20.0 MΩ ... 199.9 MΩ / 0.1 MΩ / ±(5 % of r.)

200 MΩ ... 999 MΩ / 1 MΩ / ±(10 % of r.)

1.00 GΩ ... 19.99 GΩ / 0.01 GΩ / ±(10 % of r.)

Insulation Analysis (Measuring range/ Resolution/ Accuracy)

Calculation of PI, DAR, DD:

0.01 MΩ ... 9.99 MΩ / 0.01 MΩ / ±(5 % of r. + 2 digits)

10.0 MΩ ... 100 MΩ / 0.1 MΩ / ±(5 % of r.)

RCD Test (Measuring range/ Resolution/ Accuracy)

RCD Uc (Contact Voltage):

0.00 V ... 19.99 V / 0.1 V / (-0 %/+15 %) of r. ± 10 digits

20.0 V ... 99.9 V / 0.1 V / (-0 %/+15 %) of r.

RCD (t) (Trip Time) (Measuring range/ Resolution/ Accuracy)

0.00 ms ... 40.0 ms / 0.1 ms / ±1 ms

0.0 ms ... max. time / 0.1 ms / ±3 ms

RCD I Ramp (Trip Current):

0.2×IΔN ... 2.2×IΔN / 0.05×IΔN / ±0.1×IΔN

Impedance (Measuring range/ Resolution/ Accuracy)

Zline (L-L, L-N) & Zloop (L-PE):

0.00 Ω ... 9.99 Ω / 0.01 Ω / ±(5 % of r. + 5 digits)

10.0 Ω ... 99.9 Ω / 0.1 Ω / ±(10 % of r.)

100 Ω ... 999 Ω / 1 Ω / ±(10 % of r.)

1.00 kΩ ... 9.99 kΩ / 10 Ω / ±(10 % of r.)

Voltage & Frequency (Measuring range/ Resolution/ Accuracy)

Voltage TRMS:

0 V … 550 V / 1 V / ±(2 % of r. + 2 digits)

Frequency:

0.00 Hz ... 9.99 Hz / 0.01 Hz / ±(0.2 % of r. + 1 digit)

10.0 Hz ... 499.9 Hz / 0.1 Hz / ±(0.2 % of r. + 1 digit)

Earth Resistance (Measuring range/ Resolution/ Accuracy)

3-wire Method:

0.00 Ω ... 19.99 Ω / 0.01 Ω / ±(5 % of r. + 5 digits)

20.0 Ω ... 199.9 Ω / 0.1 Ω / ±(5 % of r. + 5 digits)

200.0 Ω ... 9999 Ω / 1 Ω / ±(5 % of r. + 5 digits)

2-clamp Method:

0.00 Ω ... 19.99 Ω / 0.01 Ω / ±(10 % of r. + 10 digits)

20.0 Ω ... 30.0 Ω / 0.1 Ω / ±(20 % of r.)

30.1 Ω ... 39.9 Ω / 0.1 Ω / ±(30 % of r.)

General Data

Power Supply: 9 VDC (6 x 1.5 V battery or accu, size AA)

Overvoltage Category: 1000 V DC CAT II; 600 V CAT III; 300 V CAT IV

Protection Class: Double insulation

COM Port: BT, USB, RS232

Display: 4.3 inch Colour TFT touch screen

Dimensions (L x H x W): 230 x 103 x 115 mm

Weight: 1.3 kg


Standard set

• Instrument MI 3152H EurotestXC

• Plug commander, 1.5 m

• 2.5 kV test lead, 2 x 1.5 m

• Test lead, 3 x 1.5 m

• Power supply adapter + 6 NiMH rechargeable batteries, type AA

• Test probe, 4 pcs (blue, black, green, red)

• Crocodile clip, 4 pcs (blue, black, green, red)

• Earth set 20 m

• RS232 - PS/2 cable

• USB cable

• Soft carrying bag

• Soft carrying neck belt

• Short instruction manual

Datasheet

Stay Updated with Offers

Get exclusive volume discounts, bulk pricing updates, and new product alerts delivered directly to your inbox.

By subscribing, you agree to our Terms of Service and Privacy Policy.

Quick Support

Direct access to our certified experts