Metrel MI 3280 Transformer Testing (80 V,..., 1 V; 55, 65, 70 Hz)
TURN RATIO (r, rA, rB, rC)
Excitation voltage 80 V (Measuring range/Resolution/Accuracy):
0.8000 ... 9.9999 / 0.0001 / ±(0.2% of reading + 2 digits)
10.000 ... 99.999 / 0.001 / ±(0.2% of reading + 2 digits)
100.00 ... 999.99 / 0.01 / ±(0.2% of reading + 2 digits)
1000.0 ... 1999.9 / 0.1 / ±(0.5% of reading + 2 digits)
2000.0 ... 3999.9 / 0.1 / ±(0.5% of reading + 2 digits)
4000.0 ... 8000.0 / 0.1 / ±(1.0% of reading + 2 digits)
Excitation voltage 40 V (Measuring range/Resolution/Accuracy):
0.8000 ... 9.9999 / 0.0001 / ±(0.2% of reading + 2 digits)
10.000 ... 99.999 / 0.001 / ±(0.2% of reading + 2 digits)
100.00 ... 999.99 / 0.01 / ±(0.2% of reading + 2 digits)
1000.0 ... 1999.9 / 0.01 / ±(0.5% of reading + 2 digits)
2000.0 ... 3999.9 / 0.1 / ±(0.5% of reading + 2 digits)
4000.0 ... 8000.0 / 0.1 / n/a
Excitation voltage 10 V (Measuring range/Resolution/Accuracy):
0.8000 ... 9.9999 / 0.0001 / ±(0.2% of reading + 2 digits)
10.000 ... 99.999 / 0.001 / ±(0.2% of reading + 2 digits)
100.00 ... 999.99 / 0.01 / ±(0.5% of reading + 2 digits)
1000.0 ... 8000.0 / 0.1 / n/a
Excitation voltage 5 V (Measuring range/Resolution/Accuracy):
0.8000 ... 9.9999 / 0.0001 / ±(0.2% of reading + 2 digits)
10.000 ... 99.999 / 0.001 / ±(0.2% of reading + 2 digits)
100.00 ... 999.99 / 0.01 / ±(0.5% of reading + 2 digits)
1000.0 ... 8000.0 / 0.1 / n/a
Excitation voltage 1 V (Measuring range/Resolution/Accuracy):
0.8000 ... 9.9999 / 0.0001 / ±(0.2% of reading + 2 digits)
10.000 ... 99.999 / 0.001 / ±(0.5% of reading + 2 digits)
100.00 ... 999.99 / 0.01 / n/a
1000.0 ... 8000.0 / 0.1 / n/a
EXCITATION CURRENT (i, iA, iB, iC)
Test frequency (55, 65 or 70 Hz) (Measuring range/Resolution/Accuracy):
0.10 mA ... 9.99 mA / 0.01 mA / ±(2 % of reading + 0.20 mA)
10.0 mA ... 99.9 mA / 0.1 mA / ±(2 % of reading + 2 digits)
100 mA ... 999 mA / 1 mA / ±(2 % of reading + 2 digits)
1.00 A ... 1.10 A / 0.01 A / ±(2 % of reading + 2 digits)
PHASE DEVIATION (fi, jA, jB, jC)
Test frequency (55, 65 or 70 Hz) (Measuring range/Resolution/Accuracy):
-180.00 ... 180.00 ° / 0.01° / ±(0.05°)
WINDING RESISTANCE (R, RA, RB, RC)
Test current (10 mA ... 1000 mA) (Measuring range/Resolution/Accuracy):
1.0 mΩ ... 999.0 mΩ / 0.1 mΩ / ±(2 % of reading + 3 digits)
1.000 Ω ... 9.999 Ω / 0.001 Ω / ±(2 % of reading + 2 digits)
10.00 Ω ... 99.99 Ω / 0.01 Ω / ±(2 % of reading + 2 digits)
100.0 Ω ... 999.9 Ω / 0.1 Ω / ±(2 % of reading + 2 digits)
GENERAL SPECIFICATIONS
Battery power supply: 14.4 V DC (4.4Ah Li-ion)
Battery charging time: typical 4.5 h (deep discharge)
Mains power supply: 90-260 VAC, 45-65 Hz, 100 VA (300 V CAT II)
Protection classification: reinforced insulation
Measuring category: 50 V CAT IV
Pollution degree: 2
Degree of protection: IP 65 (case closed), IP 54 (case open)
Dimensions (w x h x d): 360 x 160 x 330 mm
Weight: 8.8 kg, (with battery and accessories)
Get exclusive volume discounts, bulk pricing updates, and new product alerts delivered directly to your inbox.
By subscribing, you agree to our Terms of Service and Privacy Policy.
Direct access to our certified experts

