Get exclusive volume discounts, bulk pricing updates, and new product alerts delivered directly to your inbox.
By subscribing, you agree to our Terms of Service and Privacy Policy.
Direct access to our certified experts
Get exclusive volume discounts, bulk pricing updates, and new product alerts delivered directly to your inbox.
By subscribing, you agree to our Terms of Service and Privacy Policy.
Direct access to our certified experts

SPECIFICATIONS - CURRENT DETECTION PART
Sensoring Method: Flexible Split-Core Type
Inside Diameter: φ210mm (total length approx. 650mm)
Influence of Residual Current: Less than 0.25A (at AC 50A, the point where influence is most receivable)
Withstanding Voltage: AC 2200V/1 minute
Length of Lead Wire: Approx. 2m between CT and Measuring Part
SPECIFICATIONS - MEASURING PART
Measuring Function: AC Line Current, AC Leakage Current
Measuring Method: Dual Integration Mode
Measuring Range AC 1000mA/10A/100A/1000A (50/60 Hz)
Range Selection: 4 Range Manual by Rotary Switch
Sampling Rate: 2 Times/sec.
Display: LCD max. 9999 reading with annunciators
Over Range Indication: "OL" mark on LCD
Data Hold Indication: "DH" mark on LCD
Low Battery Indication: "B" mark on LCD
Data Hold Function: by "DH" Switch
Filter Function: by Filter Switch to cut hi-frequency (Low Pass Filter for cut off 150 Hz)
Backlight Function: By pressing this switch, back light appears on LCD display and will get off by pressing this switch once again.
Signal Output: DC 100mV full scale to each range (Output impedance : less than 10KΩ)
Auto Power Off: Approx. 10 minutes after power on (this function is cancelled in case of using recorder cable for signal output)
SPECIFICATIONS - GENERAL SPECIFICATION
Circuit Voltage: Less than AC 600V
Operating Temperature: 0~40℃, < 80%RH without condensation
Storage Temperature: -10~60℃, < 70%RH without condensation
Withstanding Voltage: AC 2200V/1 minute
Power Supply: 1.5V (“AA” size, UM-3) x 6
Dimension (Measuring Part): 159(W)×105(H)×53(D) mm
Standard accessories: Battery (UM-3 x 6), Instruction Manual , Carrying Case
SPECIFICATIONS - ACCURACY
Accuracy:
23℃±5℃, less than 80%RH
±3%rdg±5dgt (1000mA)
±2.5%rdg±5dgt (10A/100A/1000A)
Signal Output ±2% F.S.
Resolution
0.1mA (1000mA)
0.001A (10A)
0.01A (100A)
0.1A (1000A)