Rated voltage range of SLC input power (S+,S-): 22.0 to 24.0V
Maximum SLC 24 VDC standby current (S+,S-): 250µA
Maximum SLC 24 VDC alarm current (S+,S-): 1mA
Operating voltage of external power supply line (24+,24-): 24V
Output voltage range of IDC (A+,A-,B+,B-) : 15.7 to 22.6V
Maximum module standby current of IDC 24 VDC (24+,24-): 8.5mA in Style B, 4.9mA in Style D
Maximum detector standby current of IDC 24 VDC (24+,24-): 2.4mA
Maximum module and detector alarm current of IDC 24 VDC (24+,24-): 50.0mA
Applicable IDC wiring style: Class A (Style D), Class B (Style B)
Maximum wiring resistance of IDC: 100Ω
Maximum wiring capacitance of IDC: 1µF
End-of-line resistor for IDC in NFPA Style B wiring: 5.1kΩ, 1/2W
Maximum alarm reset voltage: 0V
Minimum alarm reset time: 1.1 second
Operating temperature range: 0°C to 49°C (32°F to 120°F)
Operating humidity range: 0 to 93% (non-condensing)
Dimensions: 106mm (4.17 inches) (H) × 106mm (4.17 inches) (W) × 29mm (1.14 inches) (D
Applicable electrical box for installation: North American 64mm (2-1/2 inches) deep 2-gang box
Standard 4 inches square box 38mm (1-1/2 inch) deep box