Produal KLU Outdoor Humidity Transmitter (0…100.0 %RH, -50.0…50.0 °C)
Power supply: 24 Vac/dc (21…28 V)
Power consumption: 2 W (all options included)
Humidity measurement
Range: 0…100.0 %rH
Accuracy (25 °C): ±2 %rH (20…80 %rH), max. ±3 %rH (determined based on the voltage output signal of the analogue output).
Long-term stability: ±1 %rH / 2 years
Temperature measurement
Range: -50.0…50.0 °C
Accuracy (25 °C): ±0.5 °C (determined based on the voltage output signal of the analogue output).
Controller
Controller type: P/PI
Control functions: The controller can control humidity or temperature.
Analogue outputs: This device has 2 output connectors.
Voltage outputs
Range: 0…10 / 2…10 / 0…5 Vdc, 2 mA
Output signals: Humidity measurement, temperature measurement and control output signal.
Current outputs
Range: 4…20 mA, ≤ 500 Ω
Output signals: Humidity measurement, temperature measurement and control output signal.
Protocol: Modbus RTU
Interface: RS-485
Bus speed: 9600*/19200/38400 bit/s
Data bits: 8