Display: LED, 2 x 4 digits
Sensor Type: J,K,T,S,R type T/C, Pt100 selectable
Measuring Range: -100 .. 600 °C, J type T/C, (Inpt=J)
-100 .. 1300 °C, K type T/C, (Inpt=k)
-100 .. 400 °C, T type T/C, (Inpt=t)
0 .. 1750 °C, S type T/C, (Inpt=S)
0 .. 1750 °C, R type T/C, (Inpt=r)
-100 .. 600 °C, Pt100, (Inpt=Pt)
-99.9 .. 600.0 °C, Pt100, (Inpt=Pt.0)
Resolution ± 1 ƻC or ± 0.1 ƻC
Error: ± % 0.3
Control form: ON-OFF or P,PI,PD,PID
Output: Relay (NO + NC), 250VAC, 2A, (optional SSR)
Alarm output: Relay (NO), 250VAC, 2A
Temp. SET: Lo.L .. UP.L °C (H.Set)
Alarm SET: AL.tY = Abs,-Abs; Lo.L .. UP.L °C (A.Set)
AL.tY = rel, -rel, bnd, -bnd, bn.i, -bn.i;
-100 .. +100 / -10.0 .. +10.0 (Pt.0)
Heat Hysteresis : 0 .. 50 / 0.0 .. 5.0 ƻC (H.Hys); PID is active if set to 0
Alarm Hysteresis : 1 .. 50 / 0.1 .. 5.0 ƻC (A.Hys)
Proportional Band : 1 .. 130 ƻC (Pb.C)
Integral Time : 0 .. 30,0 min (OFF if set to 0)
Derivative Time : 0.. 10,0 min. (OFF if set to 0)
Control Period : 4 .. 200 sec (Ct)
Ofset : -100..+100 C / -10.0 .. +10.0 (oFFS)
Heating/Cooling : selectable (Only ON-OFF control form is active for cooling)
Cold. Junc. Comp. : 0 .. 50 °C (T/C)
Line Comp. : 10 Ohm max. (3 telli Pt100)
Opwerating Tepmp.: 0 .. 50 °C
Operating Voltage: 100…240VAC
Opterating Frequency: 50Hz / 60Hz
Power Consump.: < 6VA
Dimension: 46mm x 46mm
Mount: front Panel