TSURUGA 8528A AC Withstand Voltage Tester (5 kV)
Test Voltage
Output Voltage: AC 0 to 2.5 kV / 0 to 5 kV, 2 ranges
Output Capacity: 500 VA (5 kV, 100 mA)
Note: For output current 50 mA within 30 min.
Waveform: Commercial power supply waveform
Voltage Fluctuation Rate: Less than 15 % (no load → maximum load)
Voltage Output Method: Zero cross input switch
Output Voltage Setting: Manual setting with volt slider
Voltage Measurement
Rectification Method: Average effective value display
Analog Indicator: Scale: AC 0 to 5 kV
Accuracy: ± 5 % (JIS C 1102)
Digital:
Display range: AC 0.00 to 6.00 kV Green LED
Output voltage is displayed during test, the judgment value is retained after the end of test.
Accuracy: ± 1.5 % of F.S. (at F.S. 2.5 kV or 5 kV)
Current Measurement
Rectification Method: Average effective value display
Measuring Range: 0.01 to 110.0 mA
Display: 3.5 digit (1999) digital display Green LED
Leakage currentis displayed during test, the judgment value is retained after the end of test.
Resolution:
AC: 0.01 mA (0.1 to 9.9 mA), 0.1mA (10.0 to 110.0 mA)
DC: 0.01 mA (0.1 to 11.0 mA)
( ) indicates upper limit setting value
Measuring Accuracy: Upper limit setting value ± (5 %+20 μA)
Scale:
AC: 0.01 to 199.9 mA, 2 ranges
DC: 0.01 to 19.99 mA
Digital display Green LED
Leakage currentis displayed during test, the judgment value is retained after the end of test.
Resolution:
0.01 mA (0.1 to 9.9 mA), 0.1mA (10.0 to 110.0 mA)
( ) indicates upper limit setting value
Test Result Judgment
Judgment Method:
Upper limit: Analog comparator
Upper/lower limit: Digital comparator
Setting Range:
Upper limit: AC 0.1 to 110.0 mA
Lower limit: AC 0.0 to 109.0 mA
With ON/OFF function for lower limit
Resolution: 0.1mA
Judgment Conditions:
Upper limit > display value > Lower limit ... GOOD
Upper limit ≦ display value ... HIGH NG
Lower limit ≧ display value ... LOW NG
Test Time
Setting Range: 0.5 to 999 s (with Timer OFF function)
Setting Resolution: 0.1 s (0.5 to 99.9 s), 1 s (more than 100 s)
Time Display: Timer ON: Remaining time is display
Timer OFF: Elapsed time is display
Accuracy: ± 20 ms (0.5 to 99.9 s), ± 200 ms (more than 100 s)
Data Output
Voltage Monitor Output ... Output voltage can be obatained for monitoring.
Monitor Output: DC 0 to 5 V (corresponding to AC 0 to 5 kV)
Accuracy: ± 1.5 % of F.S.
RS-232C Output ... Test conditions and test results can be output.
※Utility software (option) is available.
Connector: D-sub 9P
Transmission Method: Full duplex synchronization
Transmission Speed: 9600 bps
Data Length: 8 bit
Parity: None
General Specifications
Power Supply: AC100V 50/60Hz 220 V
Power Supply Voltage Tolerance: AC 90 to 110 V
Power Consumption: Rated load: approx. 650 VA
No load (standby state): approx. 16 VA
Operating Ambient Temperature: 0 to 40 °C
Operating Humidity Range: 20 to less than 80 %RH (no condensation)
Storage Temperature: -20 to 70 °C Less than 90 %RH (no condensation)
Withstand Voltage: Between power supply and Outer box: AC 1000 V 1 minute
Size320(W) × 165(H) × 365(D )mm
Weight: Approx. 17 kg (Approx. 5.5kg is added for optional power supply models.)