Power Source
Meter: DC9V 6 nodes AA alkaline battery LR6;
Detector: Zinc manganese dry battery 6F22, 9V
Phase Checking Method
Contact phase checking: When the bare wire voltage is less than 35kV, or less than 220kV with a safety insulation sheath wire, adopt contact phase checking. (operating with an insulation rod)
Noncontact phase checking: When the bare wire voltage is more than 35kV, adopt noncontact phase checking. The probe gradually approach wire phase checking
Transmission Method: wireless transmission, about 30 meters distance of straight transmission
Phase Judge: In phase:-25°~25°; out of phase: 95°~145° and 215°~265°
Phase Checking Voltage: 200V~220kV
Phase Range: 0.0°~360.0°; accurate: ≤±12° ; Resolution: 0.1°
Frequency Range: 45.0Hz~65.0Hz; accurate: ≤±2Hz ; Resolution: 0.1Hz
Emission Frequency: 433MHz, 315MHz
LCD: 3.5-inch color LCD; display domain: 71mm×51mm
Phase Indicator: Phasor diagram and digital display meanwhile
Working Indicator: sound-light indication function, red double flashing lights and buzz like "beep - beep - beep"
Display Rate: 2 times/s
Data Storage: 9999sets (power down or replace battery will not lose data)
Automatic Shutdown: About 5mins after startup, the instrument will be automatically shut down