Technical Data:
Testing:
Output voltage:
DC: 0 to ±260 kV
Option AC: 0 – 190 kVrms
Output current (continuous):
DC: ±4 mA
Option AC: 9 mArms
Short-circuit current:
DC: ±20 mA
Option AC: 20 mArms
Accuracy:
Voltmeter (kV): 2.5%
Ammeter (mA): 2.5%
General:
Power supply:
200 – 260 V, 50/60 Hz
Option: 100 – 130 V, 50/60 Hz (with external auto transformer)
Power consumption:
Normal: 2,600 VA
In short-circuit: 5,000 VA
Ambient temperature (operational): 0°C to +45°C
Storage temperature: -20°C to +60°C
Relative humidity: Non-condensing
Dimensions:
Operating unit (W x H x D): Approx. 506 x 258 x 319 mm, (19“, 5 RU)
HV unit (Height / Diameter): Approx. 2,055 mm / Ø ca. 1,265 mm
Weight:
Operating unit: Approx. 19 kg
HV unit: Approx. 280 kg
Safety and EMC:
CE-compliant in accordance with Low Voltage Directive (2014/35/EU), EMC Directive (2014/30/EU), EN 60068-2-ff Environmental testing
Standard delivery
▪ PGK 260 HB AC/DC HV test set
▪ GDR 260-1750 discharge and earth rod
▪ Connection cable, 5 m, for connecting the HV unit to the operating unit
▪ HV connection cable, 2.5 m, with connection clip
▪ Rectifier rod for DC voltage operation, screwed into the HV unit
▪ Wrench for changing the rectifier and resistance rod
▪ Earth cable, 3 m, with earth terminal
▪ Mains supply cord, 2.5 m
▪ User manual