For full functionality of this site it is necessary to enable JavaScript.

BAUR PHG 70 TD VLF Diagnostics System (0 – 38 kVrms)

Dissipation factor measurement PHG 70 TD

VLF truesinus®: 0 – 38 kVrms

Load range: ≥10 nF

Measurement range: 0.1 x 10^-3 – 1,000 x 10^-3

Accuracy: 1 x 10^-4

Resolution: 1 x 10^-6 (mean value of the dissipation factor)

Detection and compensation of leakage currents: Automatically via the VSE box

Calibrator

Electrical charge (pulses)

CAL1B: 0.1 / 0.2 / 0.5 / 1 / 2 / 5 / 10 nC

CAL1E: 0.5 / 1 / 2 / 5 / 10 / 20 / 50 nC

Power supply: 9 V block battery, DIN/IEC 6F22

BAUR Software 4

Information about the BAUR Software 4 and the system requirements can be found in the data sheet for BAUR Software 4 cable testing and diagnostics.

General

Display: TFT monitor acc. to quotation

Power supply:

200 – 260 V, 50/60 Hz

Option: 100 – 140 V, 50/60 Hz with auto transformer

Max. power consumption: 3,500 VA

Ambient temperature (HV generator): -20°C to +55°C

Storage temperature (HV generator): -30°C to +70°C

Relative humidity: > 90%, non-condensing

Dimensions (W x H x D) (HV generator): Approx. 483 x 623 x 775 mm

Weight

HV generator: Approx. 160 kg

Total: From 250 kg (depending upon equipment)

Safety and EMC: CE-compliant in accordance with Low Voltage Directive (2014/35/EU), EMC Directive (2014/30/EU), EN 60068-2-ff Environmental testing

Standard delivery

The standard delivery depends on the quotation.

Details

Datasheet 

  • Quality Engagement
  • Easy change and return
  • Delivery Avaliable
  • Favorable payment

Apply your mail to get promotion information