For full functionality of this site it is necessary to enable JavaScript.

Precision Wave PWAVE212 Tuning Fork Level Switch (50 ~ 2000 mm)

Application: liquid point measurement

Measurement range: (50 ~ 2000) mm

Process connection: screw thread, flange

The process temperature:

Conventional type: ( 50 ~ 150 ℃)

High temperature type: (50 ~ 250 ℃)

Process pressure: (-0.1 ~ 5.0) MPa

Frequency range: about 1200Hz

Output signal: two sets of normally open and normally closed contact

Contact capacity: 24V DC/8A; AC 220 v / 5 a

Explosion-proof grade: Exd IIC T6

Protection class: plastic IP66/aluminum IP67

Details


  • Quality Engagement
  • Easy change and return
  • Delivery Avaliable
  • Favorable payment